7.2.2 Adjusting the control range via potentiometer “Pband”
The control response can be adjusted to the system conditions with this setting
- small control range = greater amplification and shorter control times
- big control range = longer control times and higher controller stability
♦
At active sensors with 0-10 V or 4-20 mA (factory setting)
5-30 % ^ 5-30 % of measuring range of the sensor
Setting range:
E.g., pressure control with PKDM:
Pressure sensor, type MBG-30I (0-30 bar, measuring range 30 bar)
Setting 10 % ^ 3 bar
♦
At passive temperature sensor TF.. (KTY10-6)
- PKDT5
5-30 % ^ 4 ... 24 K (5-30 % of device´s measuring range 0-80° C)
- PKDM
5-30 % ^ 5 ... 30 K (5-30 % of device´s measuring range -25 ... +75° C)
7.2.3 Min. speed „n-min“ (minimum output voltage or basic speed)
If required setting of a minimum output voltage, e. g. basic speed (minimum airflow rate) of connected fans.
Setting range:
From the counter-clockwise limit = “0“ (no “n-min“) to 15-100 % (^ approximately the mains voltage applied).
7.2.4 Max. speed „n-max“ (derating) and Cos
φ
-adjustment
If required setting of a maximum output voltage, e. g. speed limiter.
Setting range:
From the clockwise limit (100 %) to 20 % (^ approx. 100 % -20 % of the applied mains voltage).
For a given minimum output voltage to the setting “n-min“. For cos
ϕ
adjustment, turn “n-max“ counter-
clockwise such that the maximum output voltage will just be measured (with TRUE-RMS multimeter). This
adjustment must be made for maximum output from the fans. All flaps must be opened when using
centrifugal fans.
Cos
ϕ
adjustment
The output voltage from the unit depends on the inductance of the motor (cos
ϕ
). By this, the
maximum output voltage can already be reached below the maximum input signal
(<10 V / 20 mA). A correction is possible by setting “n-max" (cos
ϕ
adjustment).
Pband
5
30
%
16
20
24
Temperature
[K]
4
8
12
Pband
[%]
5
10
15
20
25
30
30
30
15
20
25
5
10
15
20
25
Pband
[%]
Temperature
[K]
5
10
n-min
0
100
%
n-max
0
100
%