6. General settings and operating elements
6.1 Programming the operating mode (speed controller / P- controller)
It is possible to use the device as a
speed controller
or as a
P-controller
.
Selection of the function must first be made by setting the internal
dipswitch
and
jumper or sliding switches
(depending on version).
Caution: not under voltage! Observe the safety notices!
Changed functions become active partly only after renewed switching on the mains voltage !
Factory setting: Operation as P-controller for sensor with 4-20 mA signal at “E1”!
General setting for:
Speed controller
P-Controller
Input 0-10 V
(0-20 mA / 4-20 mA and
Inverting
)
Electrical connections:
External speed setting“)
Temperature
sensor
TF..(KTY10-6)
Pressure
sensor
4-20mA
DSF../MBG
Pressure
sensor
0-10 V
Dipswitch
S1
Function: Setting:
Function: Setting:
1
Signal
function
ON = 10-0 V
OFF = 0-10 V
Control function
ON = Increasing output voltage for
decreasing actual value
OFF = Increasing output voltage for
increasing actual value
2
No function
-
Min. air shut
down
ON = not activ
OFF = activ
3
Type of
control
ON =
Internal pot
OFF = external pot or
0-10 V
Type of signal
(for
PKDT5
no
function)
OFF
ON=
4-20mA
OFF=
0-20mA
ON =
2-10V
OFF
= 0-10V
4
For speed
controller
ON
For P-controller
OFF
Additional functions
5
Hardstart
Function
(for
PKDT5
no Funktion)
ON = with
Hardstart function
OFF = no
Hardstart function
Hardstart Function
(for
PKDT5
no
Funktion)
ON = with Hardstart function
OFF = no Hardstart function
6
60 Hz
assignment
ON = 60 Hz fix
OFF =
Automatic detection
60 Hz
assignment
ON = 60 Hz fix
OFF = Automatic detection
7
Input E2
(for
PKDT5
no Function)
OFF = input not aktiv
ON = input activ
Input E2
(for
PKDT5
no
Function)
OFF = input not activ
ON = input activ
8
Phase
monitoring
ON =
phase monitoring activ
OFF =
phase monitoring
deactivated
Phase monitoring
ON =
phase monitoring activ
OFF =
phase monitoring deactivated
E1 + E2
E2.1+E2.2
+
E1.1+E1.2
Type of signal
0-10 V
switch middle or both
jumper not inserted
Depending on
type of sensor
Switch up or
both jumper up
inserted
Switch
down or
both jumper
down
inserted
Switch
middle or
both jumper
not inserted
XXXXXXX = Connector position set at the factory
ON
OFF
1
2
3
4
5 6
7
8
Dipswitch S1
jumper E1.1 / E1.2 or switch E2 for input E1
Standard input
jumper E2.1 / E2.2 or switch E2 for input E2
input for additional functions (only PKDM)
E1.1 E1.2
E2.1 E2.2
E1
V
°C
mA
E2
V
°C
mA