9.10.6.15
Timer function overwrite
|
21D
|
The timer output can be overwritten for a settable time with a selectable status if required (see timer).
To overwrite the timer function by pressing keys until the next timing change =>
“
Override Time
”
=
0 min.
The override time is activated by pressing a key at a digital input (example for D1 not inverted). The
bypass time can be ended prematurely by pressing another key.
If the contact remains closed, the override time also run out, then a short interruption is required to
reactivate.
24V
D1 D1
Limit ON: n = 0 - 80 %
Limit OFF: n = 0 - 100 %
11.09.2013
v_override_timer_3d_limit.vsd
Limit (3D)
Controller Setup
Override Timer
Contact depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
Example: speed limitation over Timer (Function
|
3D
|
)
The timer limits the maximum speed for a certain period of time (e.g. timer ON from 6:00 - 10:00 am).
With the
“
Override Timer
”
contact the limitation (from 6:00 - 10:00 am) activated by the timer can be
cancelled for an adjustable period
“
Override Time
”
(see timer / timer function overwritten: Override
Status = OFF)
To activate the limitation outside the programmed time (10:01 - 5:59 am) =>
“
Override Status
”
= ON
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E255-GB 1901 Index 001
Part.-No.
84/121