Base setup
E1 Analog In
The sensor input is factory set for mode
6.01
to sensor type
“
MAL1
”
.
Measuring range: 0...1 m/s
Output signal: 0 - 10 V
Connection terminals:
“
E1
”
,
“
GND
”
,
“
24V
”
Other settable sensors / measuring ranges:
•
MAL10 (0...10 m/s, output signal 0 - 10 V)
•
MAL15 * (0...15 m/s, output signal 0 - 10 V)
•
MAL20 * (0...20 m/s, output signal 0 - 10 V)
•
0 - 10 V, 0 - 20 mA, 4 - 20 mA (for sensors with free measuring range and linear
characteristic)
The sensor measuring range must be entered for sensors with free measuring range in
order to display the actual value correctly.
Example 0 - 10 V sensor and measuring range 0 - 5 M/s:
E1 Analog In = 0 - 10 V, E1 Unit = m/s, E1 Decimals = 1, E1 Min. = 0,0 m/s, E1 Max. =
5 m/s
* Alternative measuring ranges which can be selected by jumpers for sensor type
MAL10.
MAL1
E1 Analog In
Base setup
E1 Offset
Sensor calibration with calibrated comparison device.
The current
“
E1 Actual
”
is displayed including the offset set here.
0.00 m/s
E1 Offset
Base setup
E1 Setpoint min
(function depending on the software version available)
Limitation of the adjustable setpoint (see settings for operation)
Setting range: in measuring range of sensor
Factory setting: minimum measurement value
0.00 m/s
E1 Setpoint min
Base setup
E1 Setpoint max
(function depending on the software version available)
Limitation of the adjustable setpoint (see settings for operation)
Setting range: in measuring range of sensor
Factory setting: maximum measurement value
1.00 m/s
E1 Setpoint max
Base setup
Adjustable
“
E2 Function
”
•
|
1E
|
= external setpoint e.g. by external signal (0 - 10 V) instead of setting
“
Setpoint 1
”
. 0 - 10 V
0 - 100 % sensor measuring range.
•
|
2E
|
= External manual operation via external signal (0 - 10 V). Switch over
between settings on the device and external manual operation via digital input (see
IO Setup: function
|
7D
|
).
•
|
3E
|
= Sensor average to E1
•
|
4E
|
= Sensor comparison to E1
•
|
5E
|
= Sensor difference to E1
•
|
6E
|
= sensor for outdoor temperature-dependent setpoint adaptation, pre-pro-
grammed sensor type
“
TF..
”
.
–
Menu group
“
Setting
”
additional parameter: T-Band, T-Start SA, Min. Setpoint.
–
Menu group
“
Info
”
additional parameter: Setpoint control
–
Example see setting for operation
4.01
...
4.03
/ additional menu items.
•
|
7E
|
= Measurement value = Measurement value e.g. for limit indication, display in
Info menu
“
E2 Actual
”
.
•
|
8E
|
...
|
13E
|
= sensor input for control circuit 2 see Base setup / operation
with second control circuit.
OFF
E2 Function
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E255-GB 1901 Index 001
Part.-No.
49/121