Info
Display of the active target value at which the device operates.
“
Setpoint1
”
Menu
“
Setting
”
“
Setpoint2
”
Menu
“
Setting
”
“
Ext. Setpoint
”
= setting by external signal 0-10 V. With activated manual mode the
display constantly changes between actual value and value for manual mode.
Display for operation with two control circuits:
“
1.Setpoint 1
”
or
“
1.Setpoint 2
”
for control circuit 1
“
2.Setpoint 1
”
or
“
2.Setpoint 2
”
for control circuit 2
0
°
C
Setpoint1
Info
Only for mode
4.02
,
4.03
,
5.02
with setpoint depending on outdoor temperature (E2
function =
|
6E
|
).
100.0 Pa
Setpoint control
Info
Level modulation control output.
In addition to the bar chart, the level of the output voltage is indicated.
The modulation for each control circuit is displayed in operation with two control
circuits:
“
1. Modulation
”
for control circuit 1
“
2. Modulation
”
for control circuit 2
0 %
Modulation
Info
Minimum switch-off state
“
ON
”
= switch off, if Setpoint (+/-
“
Min. cut off
”
value) is reached.
“
OFF
”
= no switch-off, i.e. operation at minimum rate.
Display for operation with two control circuits:
“
1.Minimum switch-off
”
for control circuit 1
“
2.Minimum switch-off
”
for control circuit 2
OFF
Min. switch-off
9.9
Controller Setup
9.9.1
PIN protection activate, PIN0010
Controller Setup
The adjustments for the installation in the service level can be protected against
unintentional modi
fi
cations. To do this, activate the
“
PIN protection
”
=
“
ON
”
.
In order to simplify the initial start-up operation, the service level in the factory setting is
free =
“
OFF
”
i.e. accessible without
PIN 0010
.
OFF
PIN Protection
Available menu groups with activated PIN-protection
Main menu
Start up
Setting
Protocol
If PIN-protection is switched on, it automatically becomes active after about 15 minutes without keys
being pressed.
Possibilities for early activation of PIN protection:
•
Execute the
“
Reset
”
function in the
“
Start
”
menu group.
•
By switching the mains voltage off and then on again.
Information
After installation of the device has been carried out,
“
PIN-Protection
”
should be activated =
“
ON
”
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E255-GB 1901 Index 001
Part.-No.
53/121