9.6.2
Settings for operation modes
6.01
6.01
Air velocity control, Setpoint in m/s
Settings for controller output with function
|
2A
|
(by analogue signal see IO Setup, by MODBUS see
members menu).
Main menu
Setting
Start up
Setting
Protocol
Base setup
Controller Setup
Base setup
Setpoint1
Setting range: in measuring range of sensor
Factory setting: 0.50 m/s
0.50 m/s
Setpoint1
Base setup
Set Internal2
Setting
“
Setpoint 2
”
e.g. reduced value for night operation.
Switch over setpoint 1/2 over external contact (display where no allocation:
|
- - - - -
|
see IO Setup).
- - - - -
Set Internal2
Base setup
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Setting range: in measuring range of sensor
Factory setting: 0.50 m/s
0.50 m/s
Pband
Base setup
Min. Speed
Setting range: 0...
“
Max. Speed
”
Factory setting: 0 %
0 %
Min. Speed
Base setup
Max. Speed
Setting range: 100 %...
“
Min. Speed
”
Factory setting: 100 %
100 %
Max. Speed
Base setup
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
OFF
Manual mode
Base setup
Speed manual
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (see IO Setup).
Setting range: 0...100 %
“
Min. Speed
”
...
“
Max. Speed
”
Factory setting: 100 %
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
100 %
Speed manual
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E255-GB 1901 Index 001
Part.-No.
50/121