Additional menu item for mode
5.02
with outside-temperature dependent target-setpoint
Outside-temperature dependent target-setpoint
AT
V-min.
-15 °C
T-min.
30 °C
T-Start
S1
20.09.2017
v_volume_set_dep_outtemp.vsd
S2
T-Band
[m
3
/h]
S1
Setpoint1
S2
Set Internal2
V-Min SA
Minimum air volume
T-min
Minimum temperature
T-Start
Setpoint reducing will start below this outside temperature
AT
Outdoor temperature
An outside temperature compensation can be
activated (sensor connection
“
E2
”
to
“
Analog In
2
”
) when being operated as a air volume regu-
lation device.
Through this function, the set and active Set-
point 1/2 is automatically changed proportional
to the measured outside temperature (see Info:
“
Setpoint control
”
).
Setting
T-Band SA
Temperature range in which the setpoint change continiously with outside temperature
Setting range: 0.0..100.0 K
Factory setting: 30.0 K
30.0 K
T-Band SA
Setting
T-Start SA
Setpoint reducing will start below this outside temperature
Setting range: -10.0...40.0
°
C
Factory setting: 15.0
°
C
15.0
°
C
T-Start SA
Setting
Min. Setpoint
Minimum pressure for very low outside temperature
Setting range: depending on measuring range of sensor and
“
K factor
”
Factory setting: 700 m
3
/h
700 m
3
h
Min. Setpoint
9.6
Air velocity control
6.01
9.6.1
Base setup
6.01
Main menu
Base setup
Start up
Setting
Protocol
Base setup
Controller Setup
Base setup
Mode
Mode selection
6.01
6.01
Mode
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E255-GB 1901 Index 001
Part.-No.
48/121