9.4
Pressure control airconditioning
4.01
...
4.03
9.4.1
Base setup
4.01
...
4.03
Main menu
Base setup
Start up
Setting
Protocol
Base setup
Controller Setup
Base setup
Mode
Mode selection e.g.
4.01
4.01
Mode
Base setup
E1 Analog In
The sensor input is factory set for modes of group
4
to sensor type
“
DSG200
”
.
Measuring range: 0...200 Pa
Output signal: 0 - 10 V
Connection terminals:
“
E1
”
,
“
GND
”
,
“
24V
”
Other settable sensors / measuring ranges:
•
“
DSG 50
”
,
“
DSG100
”
,
“
DSG200
”
,
“
DSG300
”
,
“
DSG500
”
,
“
DSG1000
”
,
“
DSG2000
”
,
“
DSG4000
”
,
“
DSG6000
”
, INT300, INT500 (numerical data
meas-
uring range [Pa], output signal 0 - 10 V). Type designation DSG...
pressure
sensor with new type designation MPG..
•
0 - 10 V, 0 - 20 mA, 4 - 20 mA (for sensors with free measuring range and linear
characteristic)
The sensor measuring range must be entered for sensors with free measuring range in
order to display the actual value correctly.
Example with a 0 - 10 V sensor and 0 - 400 Pa measurement range:
E1 Analog In = 0 - 10 V, E1 Unit = Pa, E1 Decimals = 1, E1 Min. = 0,0 Pa, E1 Max. =
400 Pa
DSG200
E1 Analog In
Base setup
E1 Offset
Sensor calibration with calibrated comparison device.
The current
“
E1 Actual
”
is displayed including the offset set here.
0.0 Pa
E1 Offset
Base setup
E1 Setpoint min
(function depending on the software version available)
Limitation of the adjustable setpoint (see settings for operation)
Setting range: in measuring range of sensor
Factory setting: minimum measurement value
0.0 Pa
E1 Setpoint min
Base setup
E1 Setpoint max
(function depending on the software version available)
Limitation of the adjustable setpoint (see settings for operation)
Setting range: in measuring range of sensor
Factory setting: maximum measurement value
200.0 Pa
E1 Setpoint max
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E255-GB 1901 Index 001
Part.-No.
42/121