Sensor diff. time
Sensor diff. time
If the difference between the two sensor values for the supply air temperature or between
the two sensor values for a cot exists for the duration of time set here, a fault indication is
given.
E.g. indication
“
E1-E2 deviation
”
for too great a deviation in the fresh air temperature
sensors
Factory setting: 10 min
Setting range: 1...250 min
Set protection
Set protection
Setting protection for the cot settings.
The cot menus can be selected from the standard display for the supply air temperature
with the DOWN key
▼
.
In the factory setting
“
setting protection
”
=
“
OFF
”
the setting for
“
cot ON/OFF
”
,
“
Alarm
max.
”
and
“
Alarm min.
”
is possible after selecting the desired stall.
These can be protected against unauthorised changes by PIN (1234) if required. The
setting protection must be programmed to
“
ON
”
for this, the settings can now only be
checked but no longer changed.
The cot settings are only released for about 15 minutes after entering pin 1234.
Setting only in systems without networking with ventilation computers, querying and
setting of the
“
Alarm max.
”
and
“
Alarm min.
”
values takes place in networked systems on
the ventilation computer.
Auto. acknowl.
Auto. acknowl.
Automatic acknowledgement = alarm con
fi
rmation after repaired fault.
In the factory setting
“
Auto.acknowl.
”
=
“
OFF
”
signalling by horn,
fl
ashing light and
telephone dialling device is retained even after the fault is repaired until being acknowl-
edged by the switched or by PIN 6969.
When reprogramming to
“
Auto.acknowl.
”
=
“
ON
”
no acknowledgement is necessary after
repairing the fault. This means that the horn,
fl
ashing light and telephone dialling device
are switched off automatically when there is no more fault.
In case of an existing fault and acknowledgement via the main switch or PIN, the alarm by
horn and telephone dialling device is switched off for the duration of the adjustable "alarm
pause time".
Battery check
Battery check
Automatic battery test.
The automatic testing of the accumulator is switched on at the factory, an interruption of
the connection lead causes an alarm message.
Switching off the battery test
“
Battery check
”
=
“
OFF
”
should only be done in exceptional
cases.
E1 E2 Modus
E1 E2 Modus
Function assignment sensor inputs E1 and E2.
0
= factory setting. E1 and E2 for supply air temperature, function monitoring active.
1 = E1 and E2 switched off (alarm loop operation).
2 = E1 supply air temperature sensor, E2 switched off. I.e. no mutual function monitoring!
3 = E1 is fresh air temperature sensor, E2 = temperature sensor cot 1.
4 = E1 is temperature sensor cot 1, E2 = temperature sensor cot 2. I.e. no supply air
temperature measurement!
When networked with compatible ventilation computers, the inputs
“
E1
”
or
“
E2
”
are added
to the end of the assignment when used for cot sensors.
Delay horn
Delay horn
Time span before an alarm message is signalled by the horn.
Factory setting: 0 min
Setting range: 0...250 min
Delay light
Delay light
Time span before an alarm message is signalled by the
fl
ashing light.
Factory setting: 0 min
Setting range: 0...250 min
Operating Instructions
ALARMcon
–
model series UTE-32A-L
Setting for operation
L-BAL-E251-GB 1542 Index 002
Part.-No. 00163281