8
Setting for operation
8.1
The Info menu
21:04 Freshair
↑
|
ESC
|
P
↓
Starting from the standard display of the supply air temperature you can go to the Info menu by
pressing the
P
-key
PIN input
PIN input
Settings can be released and presettings reset with PIN codes
PIN 0010
Release Installation menu (until exiting with
|
Esc
|
).
PIN 1234
Release cot settings (automatic locking after 15 min. without operation) Only necessary
if
“
setting protection
”
set to
“
ON
”
in the ALARMcon Setup.
PIN 6969
Alarm con
fi
rmation = acknowledgement, alarm message is suppressed for an adjust-
able time span (for as long as the
fl
ashing light message).
PIN 7071
Reset time for accumulator change warning message (warning again after 2 years).
PIN 7075
Device reset.
PIN 9090
Restore user setting.
PIN 9091
To save the basic user settings.
The individually made device con
fi
gurations can be saved here.
With the corresponding PIN input 9090 can be re-established.
PIN 9095
Restore factory setting = delivery status.
Event list
Event list
The last 50 alarm messages are displayed in the
“
event list
”
after switching over to
“
ON
”
. (Position
0
= latest alarm). Exit the menu with key combination for
|
Esc
|
. The
time of the message is displayed alternately with the fault message.
Alarm test
Alarm test
As long as it is
“
ON
”
the alarm horn,
fl
ashing light and the relay for the message is
activated, for example by telephone dialling device (function also in switch position
“
0
”
).
An alarm test reminder is given automatically every week. Display
“
Alarm test
”
alter-
nately with the standard display.
This signal is reset again for a week on running an alarm test. For this, set alarm test
brie
fl
y to
“
ON
”
, then back to
“
OFF
”
and check whether an alarm is given by horn,
fl
ashing light or telephone dialling device!
Set time
Set time
“
Press the P-key
”
and set the hours with the
▲
+
▼
keys, press the
P-key
to save. Now
the minutes
fl
ash and can be set with the keys
▲
+
▼
. Press the
“
P-key
”
again to
complete. The time is saved.
To set the date follow the same method as for
“
Time
”
. The date setting consists of DAY,
MONTH and YEAR.
The clock is backed up and has a reserve of 2 or 3 hours after suf
fi
cient duration with a
power supply.
Set date
Operating Instructions
ALARMcon
–
model series UTE-32A-L
Setting for operation
L-BAL-E251-GB 1542 Index 002
Part.-No. 00163281