8.3.1
ALARMcon Setup
ALARMcon Setup
↑
|
ESC
|
P
↓
Control sys. Master
Control sys. Master
0 = Off (factory setting)
For systems that are not networked with ventilation computers
1 = ON
If the ALARMcon is connected with compatible ZIEHL-ABEGG ventilation computers in a
control system (CTE/AHX-L, PTE-6/10AHQ-L, FTET4/6/10AHMQ-L). In this case the
ALARMcon communicates with the Master of the controllers and automatically determines
the number of stalls. The ALARMcon takes over the cot numbers as well as the cot
temperature and displays these accordingly.
2 = special function ON
Same as function 1 but determination of the central sum according to greatest exhaust air
percentage.
Count ZTG8-L
Count ZTG8-L
Number of connected temperature add-on modules type ZTG8-L (max. 4 hrs.).
The stalls are assigned in the setting of the number at the factory as follows:
ZTG8-L no. 1 with cot 1 - 8, ZTG8-L no. 2 with cot 9 - 16 etc.
The assignments of sensor input and cot can be changed in the Installation menus ZTG8-
L no. 1
–
4 if necessary.
The addresses of the temperature add-on modules must be set by the DIP switches on
the board (
connection of temperature sensor add-on module).
Setting range: 0...4
Factory setting: 0
Bus address
Bus address
Only for versions with integrated Web server!
MODBUS-RTU bus address of the ALARMcon in Slave mode via bus interface BUS2.
Addressing
Addressing
Only for versions with integrated Web server!
WinterSummer time
WinterSummer time
When programming to
“
ON
”
Summer time is switched over to on the last Sunday in March
and to Winter time on the last Sunday in October.
Factory setting: ON
Setting range: ON / OFF
Adjustment E1
Adjustment E1
Adjustment (offset) for
“
E1
”
sensor value. Enter difference in Kelvin reference measuring
device
Factory setting: 0.0 K
Setting range: -10...+10K
Operating Instructions
ALARMcon
–
model series UTE-32A-L
Setting for operation
L-BAL-E251-GB 1542 Index 002
Part.-No. 00163281
22/44