44
Installation and Operating Instructions
V02
7.
Use a suitable measuring device to check that no voltage is present at the AC
screw terminal blocks between L and N and L and PE.
8.
Unscrew the screws of the screw terminal blocks and the swivel nut of the
M20 cable gland, remove the AC cable .
9.
Secure the cover (screw driver type: T25,torque: 2.5Nm).
Damage to the inverter due to electrostatic discharge
•Touching electronic components can cause damage to or destroy the
inverter through electrostatic discharge.
• Ground yourself before touching any component.