PREMIER M PLUS USER MANUAL & MAINTENANCE GUIDE  

 

Approved Document No: GLT.MAN-112 

 

PAGE 6

 

Issue: 2.3      Author: NRPJ         Date: 25/5/2017 

4.3 SUMMARY OF LED COMBINATIONS AND THEIR MEANING 

 
Use the table below to determine the condition of the panel.   
 

LEDs LIT 

LED CONDITION 

PANEL STATUS 

POWER 

STEADY GREEN 

The panel is supplied with power, and has no faults / fires (System Normal) 

COMMON FLT 
ONLY 

STEADY YELLOW 

Problem with keyswitch connections 
 

COMMON FLT & 
SUPPLY FLT 

STEADY YELLOW  
STEADY YELLOW 

There is a problem with either the mains supply or the battery backup 

COMMON FLT & 
EARTH FLT 

STEADY YELLOW  
STEADY YELLOW 

There is a wiring problem. One of the cables is touching the earth screen. 

COMMON FLT & 
ZONAL FLT 

STEADY YELLOW  
STEADY YELLOW 

There is an open circuit fault in the wiring of the zone indicated. 

COMMON FLT & 
ZONAL FLT &  
GEN S/C 

STEADY YELLOW 
FLASHING YELLOW 
FLASHING YELLOW 

There is a short circuit fault in the wiring of the zone indicated. 

COMMON FLT & 
SND FLT 

STEADY YELLOW  
STEADY YELLOW 

There is an open circuit fault in the wiring of one or more of the sounder 
circuits 

COMMON FLT & 
SND FLT & 
GEN S/C 

STEADY YELLOW 
FLASHING YELLOW 
FLASHING YELLOW 

There is a short circuit fault in the wiring of one or both of the sounder circuits 

COMMON FLT & 
SYSTEM FLT 

STEADY YELLOW  
STEADY YELLOW 

A processor fault has occurred. To reset, turn keyswitch on then back off. If 
problem persists, consult your dealer. 

COMMON FIRE 
ONLY 

STEADY RED 

A manual evacuation has occurred.  
The sounders will be active. 

COMMON FIRE & 
ZONE FIRE & 
F.A.R.E. ACTIVE 

STEADY RED 
STEADY RED 
STEADY RED 

A fire has occurred in the zone indicated.  
The sounders will be active. The F.A.R.E output will be active. 

COMMON FIRE & 
ZONE FIRE & 
F.A.R.E. ACTIVE  
& DEL 

STEADY RED 
STEADY RED 
STEADY RED 
STEADY YELLOW 

A fire has occurred in the zone indicated. The F.A.R.E output will be active. 
The sounders have a delay set, and will become active after the programmed 
delay. To override the display, press delay override. 

GEN DISABLE 

FLASHING YELLOW  
(FAST – 4 HZ) 

The panel is ready for selecting disable or test mode 

GEN DISABLE 
ZONE FAULT 
ZONE DISABLE 

YELLOW FLSH 3-0-3-0  
YELLOW FLSH 3-0-3-0  
YELLOW FLSH 3-0-3-0  

The user is scrolling through zones to select which one to disable/or user has 
just enabled the zone. 

GEN DISABLE 
ZONE FAULT 
ZONE DISABLE  

STEADY YELLOW  
STEADY YELLOW 
STEADY YELLOW 

The indicated zone is disabled. 

GEN DISABLE 
DEL 

STEADY YELLOW  
STEADY YELLOW 

The Sounders are delayed by the amount set on the Rotary switch SW2. 

GEN TEST 
ZONE FAULT 
ZONE TEST 

YELLOW FLSH 3-0-3-0  
YELLOW FLSH 3-0-3-0  
YELLOW FLSH 3-0-3-0 

The user is scrolling through zones to select which one to Test. 
 

GEN TEST 
ZONE FAULT 
ZONE TEST 

STEADY YELLOW  
STEADY YELLOW 
STEADY YELLOW  

The indicated zone is in Test Mode. 

 

4.4 CHECKING THE PANELS INDICATION LEDS 

 

Turn the key switch to “Controls Enabled” position then press the LED test button.  All the LEDs on the front panel will light, and the 
panel’s internal buzzer will also sound. If any LED Does not light up, Report the fault to the engineer 

Содержание Premier M plus

Страница 1: ...PREMIER M PLUS USER MANUAL MAINTENANCE GUIDE Approved Document No GLT MAN 112 Issue 2 3 Author NRPJ Date 25 5 2017 8 24 ZONE CONVENTIONAL FIRE ALARM PANEL USER MANUAL MAINTENANCE GUIDE...

Страница 2: ...ire extinguishers if suitably trained or call the fire brigade IF IN DOUBT CALL THE FIRE BRIGADE To reset the panel press the reset button If the panel goes back into alarm silence the sounders and ca...

Страница 3: ...LARM 7 5 2 TO TURN OFF THE ALARM SOUNDERS 7 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 7 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E TO EVACUATE THE BUILDING 7 5 5 RESETTING THE PANEL...

Страница 4: ...de called according to the company evacuation procedure Alarms can come from Smoke or Heat Detectors or manually by a person operating a Manual Call Point The system is split into Zones each covering...

Страница 5: ...operating instructions etc 47 2 i 10 Ensure that there are spare parts especially Call point elements held on site 47 2 j 1 2 With the PREMIER M PLUS Range of Fire Alarm Panels we recommend the follow...

Страница 6: ...ch may have been programmed into the Panel by pressing the Sounder Delay button Putting the Panel into the Accessed state see below 4 2 ACCESSED CONTROL AVAILABLE TO AUTHORISED USERS ONLY To avoid una...

Страница 7: ...ONLY STEADY RED A manual evacuation has occurred The sounders will be active COMMON FIRE ZONE FIRE F A R E ACTIVE STEADY RED STEADY RED STEADY RED A fire has occurred in the zone indicated The sounde...

Страница 8: ...ilenced by turning the control key to Control Enable position and momentarily pressing the Start Stop button The Alarm Sounders will cease to sound but the light s for the Zone s in Alarm and the red...

Страница 9: ...a new glass element if glass type If the cause of the alarm was by detector activation e g cooking smoke the smoke will have to be cleared from the room before the panel can be reset Reset the panel...

Страница 10: ...lt zone s may not be recognised by the Fire Alarm Panel until the Fault Conditions have been cleared It can take up to 60 seconds from repairing a fault for the display to clear Short Circuit Fault If...

Страница 11: ...he panel On power up the panel looks for a signal from a repeater If it does not see one it assumes there is no repeater connected If the panel sees a repeater but then looses its signal it will show...

Страница 12: ...ash fast This means the panel is in disable enable mode 3 Press scroll switch once and this will cause the General Disablement LED Zone1 fault and Zone 1 Disablement to flash with a 3 quick flash then...

Страница 13: ...the SOUNDER DELAY LED will be lit When a zone processes an alarm signal the panel will indicate fire in the usual way but the sounders will not be active until the delay period has expired To overrid...

Страница 14: ...te 25 5 2017 User Manual Modification History Do Not Print this Page when creating PDF Of the manual ISSUE DATE CHANGES 2 1 10 11 2010 Version Before addition of modification History 2 2 23 7 2012 Dra...

Отзывы: