5. THE FIRE CONDITION
5.1 HOW THE PREMIER M PLUS INDICATES AN ALARM
When the PREMIER M PLUS Fire Alarm Panel is set into alarm by a Detector or
Manual Call Point located in a zone that is not already in alarm it will: -
Light the General Fire LED and appropriate Zone
Fire LED(s) on the front of its enclosure
Sound Internal buzzer
Start the Alarm Sounder s, F.A.R.E. and Auxiliary
RELAY outputs, (provided there is no Delay set on
the sounders).
The building evacuation procedure should now be followed.
IMPORTANT NOTE:
If a zone has been disabled, it can not be triggered into Alarm.
This should be remembered when disabling part of the system. (see Disabling zones
or sounders later in this manual).
5.2 TO TURN OFF THE ALARM SOUNDERS
The Alarm Sounders may be silenced by turning the control key to “Control Enable” position and momentarily pressing
the Start/Stop button.
The Alarm Sounders will cease to sound but the light(s) for the Zone(s) in Alarm and the red General Fire light will stay lit. The
Auxiliary Fire relay will and F.A.R.E. Output remain active. (The Panels internal buzzer can also be silenced by pressing the Silence
Buzzer button).
5.3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE
If another detection Zone is activated after the Alarm Sounders have been silenced, the panel will: -
Restart the sounders
Light the Zone Fire LED(s) for any new Zone(s) in alarm
Keep the light(s) for the previous Zone(s) in fire, and General Fire lit.
5.4 TURNING ON THE ALARM SOUNDERS FROM THE FACP (I.E. TO EVACUATE THE BUILDING).
With the control key in “Controls Enabled” position, momentarily pressing the Start/Stop will cause the Alarm sounders
to sound.
Pressing the Start/Stop button again will Silence the Alarm Sounders.
Note: If the Alarm Sounders have been disabled, pressing the Stop/Start button will have no effect.
5.5 RESETTING THE PANEL