PREMIER M PLUS USER MANUAL & MAINTENANCE GUIDE
Approved Document No: GLT.MAN-112
PAGE 5
Issue: 2.3 Author: NRPJ Date: 25/5/2017
4. PANEL INDICATIONS & CONTROLS
Two levels of control are available to the User(s) of this Fire Alarm Panel.
4.1 GENERAL CONTROLS
When the Panel is in its Normal state, the indicator lights on the front of the enclosure give a comprehensive overview of the
System’s current status. Any Fire and Fault conditions are clearly displayed, and any disablements highlighted. For detailed
descriptions of what each indicator means, please refer to the table on the opposite page.
The only functions that can be performed by the User when the Panel is in its Normal state are:
Overriding any Delays, which may have been programmed into the Panel by pressing the
Sounder Delay
button.
Putting the Panel into the Accessed state – see below.
4.2 ACCESSED CONTROL (AVAILABLE TO AUTHORISED USERS ONLY)
To avoid unauthorised changes to critical parts of the Fire Alarm System, controls such as silencing the Sounders, resetting an
Alarm condition and implementing Disablements are only accessible via a secure method of entry which puts the panel into the
Accessed state.
To put the Panel into the Accessed State:
Insert Access Control Key into the Fire alarm panel. Turn the key to the control enable
position (please note the key should not be removed when in this position). To leave the Accessed state, turn the key back to the
off position.
In the Accessed State (Access level 2), the user can start or stop the fire alarm sounders, silence the panels internal buzzer, reset
the panel, or disable or enable any part of the system.