PREMIER M PLUS USER MANUAL & MAINTENANCE GUIDE  

 

Approved Document No: GLT.MAN-112 

 

PAGE 4

 

Issue: 2.3      Author: NRPJ         Date: 25/5/2017 

 

3. USER RESPONSIBILITIES & MAINTAINENCE OF THE FIRE ALARM SYSTEM, INCLUDING THE FACP 
& ITS INTEGRAL PSE 

 

According to the British Standard Code for Fire Detection and Alarm Systems for Commercial Buildings (BS5839-1), the owner or 
person having control of the premises should appoint a responsible person to oversee the effective operation of the Fire Alarm 
System. 
 
Below is a summary of the main functions the “Responsible Person” is expected to carry out.  This summary is not intended to 
replace  Section  seven  (User  responsibilities)  of  BS5839-1  (available  from  BSI,  or  your  local  library).  It  is  meant  to  give  a  brief 
outline of user responsibilities for the safe upkeep of the Fire Alarm System.  The number in brackets shows the relevant BS5839-1 
clauses. 
 

The responsible person must:- 
 

1.

 

Have sufficient authority to carry out the duties associated with being the responsible person (47.2.a) 

2.

 

Check the system at least once every 24 hours to ensure there are no faults present (47.2.b) 

3.

 

Ensure there are arrangements for testing and maintaining the system (47.2.c) 

4.

 

Ensure the log book is up to date, and available for inspection (47.2.d) 

5.

 

Instruct  all  relevant  occupants  on  the  basic  operation  of  the  system,  including  start  evacuation,  silence  alarms,  silence 
faults and system reset (47.2.e) 

6.

 

Take appropriate action to limit the rate of false alarms (47.2.f) 

7.

 

Ensure that all detectors and manual call points remain unobstructed at all times (47.2.g) 

8.

 

Liaise  with  maintenance  personnel  to  ensure  that  cleaning,  maintenance  or  building  work  does  not  interfere  with  the 
functioning and reliability of the fire alarm system (47.2.h). 

9.

 

Ensure any changes to the system are recorded with updated drawings, operating instructions etc. (47.2.i) 

10.

 

Ensure that there are spare parts (especially Call point elements) held on site (47.2.j.1&2) 

 
With the PREMIER M PLUS Range of Fire Alarm Panels, we recommend the following tests are carried out: - 
 

Daily Inspection 

 

Check that the green Power LED is lit. 

 

If  there  are  any  yellow  fault  LEDs  lit,  or  the  green  Power  LED  is  not  lit,  report  the  fault(s)  to  the  designated  site 
maintenance engineer. 

 
Weekly Test (you may wish to temporarily disconnect the Aux relay during the following Tests) 

 

Set off a manual call point or sensor to test the Fire Alarm panel responds and all the sounders activate. 

 

Do not test the same device each week. Test a different zone each week using a different call point or detector so that 
eventually, all the devices will be tested. 

 

Reset the System by pressing Start Stop sounders, Silence Buzzer, Reset. 

 

Turn key to controls enabled. Press the LED Test button. Check that all LEDs light, and the buzzer sounds 

 

Check that no call points or fire detectors are obstructed in any way. (e.g. New furniture or decorations) 

 

Quarterly Test (to be carried out by authorised service personnel only) 

 

Check that any servicing or repairs required by all previous logbook entries has been undertaken. 

 

Visual inspection of the batteries and connections. Check the alarm sounders work on battery only. 

 

Activate a device from each zone to test the fire alarm. (As per weekly test). 

 

Annual Test (to be carried out by authorised service personnel only) 

 

Check every detector, call point, sounder and all auxiliary equipment for correct operation. 

 

Check PSU output Voltage (30V DC), Charger Voltage (27.6V off load, adjusted with VR1) & Battery Voltage (25-27V) 

 

Every Five Years (to be carried out by authorised service personnel only) 

 

Carry out a complete wiring check in accordance with the testing and inspection requirements  of the relevant National 
wiring regulations (in the UK this is the IEE Wiring Regulations). The Batteries should be replaced because SLA batteries 
have a working life of 5 years. 

Содержание Premier M plus

Страница 1: ...PREMIER M PLUS USER MANUAL MAINTENANCE GUIDE Approved Document No GLT MAN 112 Issue 2 3 Author NRPJ Date 25 5 2017 8 24 ZONE CONVENTIONAL FIRE ALARM PANEL USER MANUAL MAINTENANCE GUIDE...

Страница 2: ...ire extinguishers if suitably trained or call the fire brigade IF IN DOUBT CALL THE FIRE BRIGADE To reset the panel press the reset button If the panel goes back into alarm silence the sounders and ca...

Страница 3: ...LARM 7 5 2 TO TURN OFF THE ALARM SOUNDERS 7 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 7 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E TO EVACUATE THE BUILDING 7 5 5 RESETTING THE PANEL...

Страница 4: ...de called according to the company evacuation procedure Alarms can come from Smoke or Heat Detectors or manually by a person operating a Manual Call Point The system is split into Zones each covering...

Страница 5: ...operating instructions etc 47 2 i 10 Ensure that there are spare parts especially Call point elements held on site 47 2 j 1 2 With the PREMIER M PLUS Range of Fire Alarm Panels we recommend the follow...

Страница 6: ...ch may have been programmed into the Panel by pressing the Sounder Delay button Putting the Panel into the Accessed state see below 4 2 ACCESSED CONTROL AVAILABLE TO AUTHORISED USERS ONLY To avoid una...

Страница 7: ...ONLY STEADY RED A manual evacuation has occurred The sounders will be active COMMON FIRE ZONE FIRE F A R E ACTIVE STEADY RED STEADY RED STEADY RED A fire has occurred in the zone indicated The sounde...

Страница 8: ...ilenced by turning the control key to Control Enable position and momentarily pressing the Start Stop button The Alarm Sounders will cease to sound but the light s for the Zone s in Alarm and the red...

Страница 9: ...a new glass element if glass type If the cause of the alarm was by detector activation e g cooking smoke the smoke will have to be cleared from the room before the panel can be reset Reset the panel...

Страница 10: ...lt zone s may not be recognised by the Fire Alarm Panel until the Fault Conditions have been cleared It can take up to 60 seconds from repairing a fault for the display to clear Short Circuit Fault If...

Страница 11: ...he panel On power up the panel looks for a signal from a repeater If it does not see one it assumes there is no repeater connected If the panel sees a repeater but then looses its signal it will show...

Страница 12: ...ash fast This means the panel is in disable enable mode 3 Press scroll switch once and this will cause the General Disablement LED Zone1 fault and Zone 1 Disablement to flash with a 3 quick flash then...

Страница 13: ...the SOUNDER DELAY LED will be lit When a zone processes an alarm signal the panel will indicate fire in the usual way but the sounders will not be active until the delay period has expired To overrid...

Страница 14: ...te 25 5 2017 User Manual Modification History Do Not Print this Page when creating PDF Of the manual ISSUE DATE CHANGES 2 1 10 11 2010 Version Before addition of modification History 2 2 23 7 2012 Dra...

Отзывы: