DYCU-3 Dynameco Extinguisher Control Unit 

DOC: GLT.MAN-136 

 

5

 

ISSUE: 1 
DATE: 3/9/2009 
AUTHOR: NRPJ 

OPERATION. 
 
The DYCU-3 can be triggered in one of 2 ways:- 
 
MANUAL TRIGGERING (CALL CONNECTION) 
 
If a normally open connection to the CALL input closes (EG call point pressed), the unit 
will wait for about half a second to verify the signal. 
 
It will then operate it`s INTERNAL BUZZER. 
 
It will then operate it`s ALARM output. This can be used to drive a local sounder, or to 
signal to monitoring equipment.  
 
It will then operate Canister OUTPUT 1. (this will operate the Dynameco canister 
connected to this output).  
 
After about 0.5 second, it will turn off this output, and then turn on OUTPUT 2. (to 
trigger a second canister) 
 
After about 0.5 second, it will turn off OUTPUT 2, and then turn on OUTPUT 3. (to 
trigger a third canister). 
 
After another 0.5 second, the unit will turn off OUTPUT 3. It will continue with it`s 
internal buzzer operating, and its alarm output operating, until the Triggering signal is 
reset. 
 
AUTOMATIC TRIGGERING (REMOTE CONNECTION) 
 
For the automatic triggering, there is an option to delay the output signals by 10 seconds. 
This gives an opportunity to investigate the cause of the alarm and HOLD the system if 
necessary. This is done by setting jumper 1.  
 
With the jumper OFF there will be no delay, and the operation sequence will be exactly 
the same as for manual triggering 
 
With the jumper ON there will be a 10 second delay between the unit operating it`s 
ALARM, and operating canister output 1. The unit then follows the same sequence. 
 
HOLD 
 
The unit has a hold input. This is used to inhibit the extinguishing outputs from operating. 
It stops both Automatic & manual Triggering. 
 

Содержание DYCU-3

Страница 1: ...DYCU 3 Dynameco Extinguisher Control Unit DOC GLT MAN 136 1 ISSUE 1 DATE 3 9 2009 AUTHOR NRPJ DYCU 3 AEROSOL FIRE EXTINGUISHER CONTROL UNIT OPERATION MANUAL...

Страница 2: ...DYCU 3 Dynameco Extinguisher Control Unit DOC GLT MAN 136 2 ISSUE 1 DATE 3 9 2009 AUTHOR NRPJ INDEX INTRODUCTION 3 CONNECTIONS 4 OPERATION 5 LINKING 6 TECHNICAL INFO 7...

Страница 3: ...reaction to stop thus extinguishing the fire These canisters are electrically triggered so need to be connected to a control unit The DYCU 3 is a low cost unit designed to trigger 3 canisters from a...

Страница 4: ...Dynameco Canister OUT3 Connection to third Dynameco Canister ALARM 24V output Energises when unit triggered 24V OUT Connection to power external Detector 100mA max CALL Manual Triggering input eg Cal...

Страница 5: ...urn off OUTPUT 2 and then turn on OUTPUT 3 to trigger a third canister After another 0 5 second the unit will turn off OUTPUT 3 It will continue with it s internal buzzer operating and its alarm outpu...

Страница 6: ...ed together Either 1 2 or all 3 signals can be linked Whatever is more appropriate for type of system being designed Controller 1 Controller 2 In the above example the yellow call point would trigger...

Страница 7: ...ondensing IP RATING IP43 SIZE 234 x 165 x 80mm WEIGHT 200g ELECTRICAL MODEL DYCU 3 PART NO 83 005 SUPPLY VOLTAGE 24V DC POWER UP CURRENT 1A STANDBY CURRENT 20mA ACTIVE CURRENT 50mA 1A for Canister Seq...

Отзывы: