background image

DYCU-3 Dynameco Extinguisher Control Unit 

DOC: GLT.MAN-136 

 

6

 

ISSUE: 1 
DATE: 3/9/2009 
AUTHOR: NRPJ 

LINKING 
 
The DYCU-3 contains dual connections for each of the 3 input signals (CALL,  
REMOTE, HOLD) 
 
These allow units to be daisy-chained together. Either 1, 2 , or all 3 signals can be linked. 
Whatever is more appropriate for type of system being designed. 
 

Controller 1

Controller 2

 

 
In the above example, the yellow call point would trigger the canisters on both controller 
1 & controller 2, but an automatic trigger would only operate canisters on that specific 
controller. 
 
Note that if the HOLD signal is linked, all extinguishing on the linked system will be 
halted. 
 
 

Содержание DYCU-3

Страница 1: ...DYCU 3 Dynameco Extinguisher Control Unit DOC GLT MAN 136 1 ISSUE 1 DATE 3 9 2009 AUTHOR NRPJ DYCU 3 AEROSOL FIRE EXTINGUISHER CONTROL UNIT OPERATION MANUAL...

Страница 2: ...DYCU 3 Dynameco Extinguisher Control Unit DOC GLT MAN 136 2 ISSUE 1 DATE 3 9 2009 AUTHOR NRPJ INDEX INTRODUCTION 3 CONNECTIONS 4 OPERATION 5 LINKING 6 TECHNICAL INFO 7...

Страница 3: ...reaction to stop thus extinguishing the fire These canisters are electrically triggered so need to be connected to a control unit The DYCU 3 is a low cost unit designed to trigger 3 canisters from a...

Страница 4: ...Dynameco Canister OUT3 Connection to third Dynameco Canister ALARM 24V output Energises when unit triggered 24V OUT Connection to power external Detector 100mA max CALL Manual Triggering input eg Cal...

Страница 5: ...urn off OUTPUT 2 and then turn on OUTPUT 3 to trigger a third canister After another 0 5 second the unit will turn off OUTPUT 3 It will continue with it s internal buzzer operating and its alarm outpu...

Страница 6: ...ed together Either 1 2 or all 3 signals can be linked Whatever is more appropriate for type of system being designed Controller 1 Controller 2 In the above example the yellow call point would trigger...

Страница 7: ...ondensing IP RATING IP43 SIZE 234 x 165 x 80mm WEIGHT 200g ELECTRICAL MODEL DYCU 3 PART NO 83 005 SUPPLY VOLTAGE 24V DC POWER UP CURRENT 1A STANDBY CURRENT 20mA ACTIVE CURRENT 50mA 1A for Canister Seq...