DYCU-3 Dynameco Extinguisher Control Unit 

DOC: GLT.MAN-136 

 

3

 

ISSUE: 1 
DATE: 3/9/2009 
AUTHOR: NRPJ 

INTRODUCTION 
 
The Dynameco Aerosol Generator canister is a low cost fire suppression module, that 
comes in 3 sizes:- 

                

                

 

Dynameco 200 protects an area of 2 m

Dynameco 300 protects an area of 3 m

2

 

Dynameco 2000 protects an area of 20 m

 
When triggered the canister generated a fine potassium dust that binds with free radicals 
produced by the fire, causing the physical chain reaction to stop, thus extinguishing the 
fire. 
 
These canisters are electrically triggered, so need to be connected to a control unit. 
 
The DYCU-3 is a low cost unit designed to trigger 3 canisters from a single module, 
either by the manual operation of a switch (call point or mushroom push button switch), 
or by the relay output of an automatic fire detector. 
 
Examples of automatic fire detector include:- 
 

 

Smoke detector & relay base 

 

Flame Detector 

 

Aspirating smoke detector 

 

Heat detection cable  

 

Standard fire alarm panel 

 
As the Canister requires a large current to operate (around 1 Amp), the DYCU-3 triggers 
the 3 canisters sequentially, so that only a 1 amp PSU is required. 
 
 

Содержание DYCU-3

Страница 1: ...DYCU 3 Dynameco Extinguisher Control Unit DOC GLT MAN 136 1 ISSUE 1 DATE 3 9 2009 AUTHOR NRPJ DYCU 3 AEROSOL FIRE EXTINGUISHER CONTROL UNIT OPERATION MANUAL...

Страница 2: ...DYCU 3 Dynameco Extinguisher Control Unit DOC GLT MAN 136 2 ISSUE 1 DATE 3 9 2009 AUTHOR NRPJ INDEX INTRODUCTION 3 CONNECTIONS 4 OPERATION 5 LINKING 6 TECHNICAL INFO 7...

Страница 3: ...reaction to stop thus extinguishing the fire These canisters are electrically triggered so need to be connected to a control unit The DYCU 3 is a low cost unit designed to trigger 3 canisters from a...

Страница 4: ...Dynameco Canister OUT3 Connection to third Dynameco Canister ALARM 24V output Energises when unit triggered 24V OUT Connection to power external Detector 100mA max CALL Manual Triggering input eg Cal...

Страница 5: ...urn off OUTPUT 2 and then turn on OUTPUT 3 to trigger a third canister After another 0 5 second the unit will turn off OUTPUT 3 It will continue with it s internal buzzer operating and its alarm outpu...

Страница 6: ...ed together Either 1 2 or all 3 signals can be linked Whatever is more appropriate for type of system being designed Controller 1 Controller 2 In the above example the yellow call point would trigger...

Страница 7: ...ondensing IP RATING IP43 SIZE 234 x 165 x 80mm WEIGHT 200g ELECTRICAL MODEL DYCU 3 PART NO 83 005 SUPPLY VOLTAGE 24V DC POWER UP CURRENT 1A STANDBY CURRENT 20mA ACTIVE CURRENT 50mA 1A for Canister Seq...

Отзывы: