PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70
Doc No: GLT-215-7-1 Issue: 1.36 Author: NJ/TE DATE: 25/05/2017
40
Modify Action Number 5. Total Actions 10.
Input: Panel – General Alarm.
Output: Zone – Range 1 to 3 with Outputs ON.
The * means that the Output includes a RMT Event.
ACTION MODIFICATION <0005>:001 DLY:010
I Panel
Gen Alarm
O Zone RANGE 001 To 003 Outputs ON*
[Input ][Output ][Erase ][Exit ]
The current action (i.e. 0005) can be erased by selecting the [Erase] command. In this case, actions 0006 to 0010 will then be
automatically re-numbered as actions 0005 to 0009.
See also the Menu Command Structure in Section 18.
9.1.2 LOGIC
Logic events are very similar to that of the Actions. The difference is that with Logic you are able to create “AND” statement events
with specific Points, Zones, Loops and Panels, where in Actions it does not allow you to do this. For example, if the input is a fire in
zone 2 (e.g. an optical detector gone into alarm), the system can be programmed to wait until it receives another fire indication
from a device, before it sets off its output devices. As with actions, it is the responsibility of the commissioning engineer to verify
that the programmed panel logics operate the sounders as required. The inputs and outputs can be selected from 4 categories –
Point, Zone, Loop and Panel. Example of Selecting a Logic Event (New Logic):
The following example shows LOGIC No.2 (top right of LCD) being selected. The Quatro is programmed to only activate the panel
sounders (with a 10 second delay), when points address 7 & 8 on loop 1 detect a fire.
This will be to setup the 1st event:
Select Num of Events:
2
(MAX 10 EVENTS)
Select Input Category:
Point
Select Loop:
1
Select Point Address:
007
Select Type of Input:
Alarm
This will be to setup the 2nd event:
Select Input Category:
Point
Select Loop:
1
Select Point Address:
008
Select Type of Input:
Alarm
This will be to setup the output:
Select Output Category:
Panel
Select Delay:
010
seconds
Press
More
to select output type:
Sounders ON
Select Sounder Tone:
ALARM FLASH
Press S
ounders ON
The current action (i.e. 0005) can be modified by selecting the
MODIFY LOGIC
option in the Actions menu, and its used the same
way as described above in the modify actions (section 17.2). They can also be erased in this same menu by selecting the
ERASE
option.
ACTION CREATION
0002
NUM OF EVENTS
<
02
>
[Point ]
[Zone ][Loop ][Panel ]
POINT SELECTION
0002
LOOP : <
1
> ADR : [
007
]
[
Alarm
]
[Cancel ]
ACTION CREATION 0002
INPUT SELECTION
[Point ]
[Zone ][Loop ][Panel ]
POINT SELECTION
0002
LOOP :<
1
> ADR : [
008
]
[
Alarm
]
[Cancel ]
0002
OUTPUT SELECTION
RMT EVENT :<NO>
[Point ][Zone ][Loop ]
[Panel ]
PANEL SELECTION 0002
DELAY : <
010
>
TONE : [
ALARM FLASH
]
[
Sounders ON
][More ][Cancel ]