7.1.14 ZONE LABELS 

The subdivision of a fire alarm system was explained in Section 3, the Premier Quatro panel being capable of assigning 20 zones. 
When a fire is enunciated, the zone number in which the fire is located is indicated on the alphanumeric display. In addition to its 
numerical description, a zone can be identified by a text label, e.g. 3

RD

 FLOOR WEST EXT. If the installer associates a text label with 

each zone of a fire alarm system, this will be displayed on the LCD when a fire is detected. The maximum length of the zone text 
label is 18 characters. 

To access the menu for selecting  Zone Labels: 

 

Turn the key switch clockwise to the Controls Enabled 
Position. The controls Active LED will light.  

ZONE EDIT                        
ZONE   :<XXX>   MODE       ENABLE 
TEXT   :[3RD FLOOR WEST EXT   ] 
   [ - ]   [ + ]   [Points]       [Exit]

 

 

 

Press any key followed by the level 2 password (default is 
2222). 

Select Zone edit, and then the zone number by either using the 
alphanumeric keypad, or the function keys F1 or F2 to increment or 
decrement the zone number. Type in the text label between the 
brackets on the 3rd line of the display. Selecting F3 allows one or 
more points (i.e. devices) to be added to the loop. 

ADD POINTS 
ZONE   : <XXX>       LOOP   :[1] 
RANGE  : [001]        TO    :[001] 
[Accept  ]                    [Exit   ]

 

 

The LCD also indicates the current mode of each zone – enabled or disabled. 
 

7.1.15 ADDRESS LABELS AND ZONES 

Premier Quatro is an addressable panel, i.e. it will indicate the address or location of a fire that has been detected. The address 
number of each point or device on each loop has already been selected according to its DIP switch setting. The installation engineer 
must now assign a label or location for each device, e.g. ROOM 107. A maximum of 20 characters can be used for each label. At the 
same time each point can be allocated to a zone. 
To access the menu for selecting Address Labels: 

 

Turn the key switch clockwise to the Controls Enabled Position. The controls Active LED will light.  

 

Press any key followed by the Password 2222.   

 

Select 

Points

 followed by 

Edit Point

. For each point the following data can be entered: 

Loop Number, Address Number, Zone Number & the Text Label (e.g. ROOM 107)  
 

The LCD also indicates the MODE of a point, i.e. ENABLED or 
DISABLED, the analogue value (V) that the device is sending to the 
panel, and the type. Pressing the 

F

 keys below [–] and [+], decreases 

or increases the address number. 

LOOP :<1>       ADR  :[019]   ZONE:[023] 
TYPE :MCP       MODE :ENABLE    V:192 
TEXT :[ROOM 107               ] 
   [ - ] 

[ + ]            [Exit     ]

 

 
When a fire is detected, the address label of the device which has been triggered can be displayed by using the keys 

 and 

to 

scroll through the list of fires detected and stored by the panel. 
 

7.1.16 PLATFORM SOUNDER (SANDWICH SOUNDER) 

The remote output on a detector is used to switch on a connected remote indicator (LED). It can also be used to trigger a “platform 
sounder” 
 
A panel cannot see a platform sounder as it does not communicate with the panel, so the panel needs to be told that the sounder is 
fitted.  

 

 

 

 

 

 

 

Turn the key switch clockwise to the Controls Enabled 
Position. The controls Active LED will light.  

 

Press any key followed by the level 2 password (default 
2222).  

 

Select 

Point

 followed by 

LED Setup

. Change Platform 

sounder field from NO to 

YES

(NOTE:  It is recommended that all detectors that do 

NOT

 have a 

platform sounder fitted are to have it set as 

Platform Sounder: 

NO

.) 

 

 

 

LOOP :<1> ADR  :[002] TYPE :MKII-AOH 
PLATFORM SOUNDE:[YES] 
    
   [ - ]    [ + ]            [Exit      ] 

         

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание Premier Quatro QT/1

Страница 1: ...INSTALLATION MANUAL Fyreye MKII Firmware Versions PANEL 1 84 LOOP 3 70 MKII PROTOCOL ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL INSTALLATION MANUAL www acornfiresecurity com www acornfir...

Страница 2: ...ERNAL LAYOUT 10 3 3 NAVIGATING THE PANEL MENUS 11 3 3 1 NAVIGATING A SET UP SCREEN 11 3 4 CONTROLS 11 3 5 INDICATING DIFFERENT PANEL STATES 12 3 5 1 THE QUIESCENT CONDITION 12 3 5 2 THE ALARM CONDITIO...

Страница 3: ...9 REMOTE LED INDICATOR 26 6 4 SETTING THE DEVICE ADDRESS DETECTORS CALL POINTS SOUNDERS AND INTERFACE UNITS 27 6 4 1 SOFT AND HARD PROGRAMMING 27 6 4 2 DIP SWITCH ADDRESS SETTINGS FULL TABLE 27 6 5 FI...

Страница 4: ...TALLER LEVEL LEVEL 2 45 10 3 CAUSE EFFECT TABLE 46 11 DISABLEMENTS 47 11 1 DISABLEMENT 47 11 2 ZONE DISABLEMENT 47 11 3 DEVICE DISABLEMENT 48 11 4 SOUNDER DISABLEMENT 48 11 5 RELAY DISABLEMENT 49 11 6...

Страница 5: ...and away from damp dirty areas e g in a small cardboard box 1 2 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL NOTE When the Quatro panel is operating normally i e not being tended by service pe...

Страница 6: ...missioned according to our guidelines and the relevant National Standards by an approved and competent person or organization the warranty may become void 2 PANEL SPECIFICATION 2 1 FUNCTIONS REQUIRED...

Страница 7: ...itch ON Installer password Configure loops Assign zones Assign Text to each point Modify Alarm Operation Programming Configure network if fitted System Diagnostics LED blink loop Auto check Change pas...

Страница 8: ...n 26 V DC MAXIMUM LOOP CURRENT 500 mA NUMBER OF LOOPS 4 MAXIMUM NUMBER OF ZONES 250 Zones MAXIMUM LOOP CAPACITY 250 Addresses MAXIMUM LOOP LENGTH 2 km MAXIMUM LOOP RESISTANCE 44 ohm 22 ohms to 22 ohms...

Страница 9: ...c No GLT 215 7 1 Issue 1 36 Author NJ TE DATE 25 05 2017 8 2 5 FUSE SPECIFICATIONS Power Supply Controller PCB Fuse Label Rating Description A_Fuse 2 5A PSU Output Channel A B_Fuse 2 5A PSU Output Cha...

Страница 10: ...Fuse Rating Description F1 NOT USED NOT USED F2 F 500 mA 24V Aux Supply Fuse F3 NOT USED NOT USED F4 F 500 mA Conventional Sounder Circuit SND 1 F5 F 500 mA Conventional Sounder Circuit SND 2 F6 F 5 A...

Страница 11: ...d with other Quatro panels or repeaters with up to 32 panels per network It has a simple Intuitive Action Programming for configuring sounder relay operations It has an optional add on TCP IP card tha...

Страница 12: ...ntered directly with leading zeros if necessary Text fields Use up down cursors to move the cursor in the string 3 4 CONTROLS The panel contains the following mandatory controls They can only be opera...

Страница 13: ...ne in fire In the example the first alarm was in Zone 3 Zone 3 is the Second Floor The 2nd line indicates the most recent zone in fire The format is the same as line 1 The most recent fire occurred in...

Страница 14: ...the general disablement LEDs are lit steady 10 12 13 13 51 DISABLED ZONES 001 001 Z001 Ground Floor In this example the addressable point at loop 1 address 1 is disabled It is a call point General di...

Страница 15: ...etter the description the easier it is to locate in the event of an alarm The panel allows 22 characters It may be necessary to use abbreviations to achieve the required label Keep the design of the s...

Страница 16: ...y a battery calculation spreadsheet is available Please contact your distributor for details 4 6 CHOOSING AUDIBLE VISUAL WARNING DEVICES There are a number of options for Audible visual Devices that c...

Страница 17: ...ect to the EVACS 16 system It sees each channel of the EVACS as a voice sounder so the panel has control over the individual channels They will be programmed as part of the usual ACTIONS programming f...

Страница 18: ...n open circuit reading Also make sure that the screen earth has continuity and is not showing an open circuit Now test between the core making sure there is no short circuit repeat this test between s...

Страница 19: ...ng the building It should be fitted to a sturdy wall that will not flex unnecessarily It should ideally be mounted at eye level in order for it to be viewed without need of a ladder It should be insta...

Страница 20: ...e Knock out cable entries can be easily removed by Tapping with a suitable screwdriver or chisel from outside the control panel box Take care not to dent or deform the metal enclosure If a grommet is...

Страница 21: ...self with the fire alarm panels controls 5 6 CONNECTING THE BATTERIES SOUNDER CIRCUIT DETECTION LOOP MAINS IN EARTH BAR Figure 4 Battery location and connection details To calculate the exact requirem...

Страница 22: ...other zone The screen cable at each end of the loop not shown below must be connected to the Panel s earth bar Figure 5 Example of addressable loop wiring top connections to loop cards bottom 6 2 ADDR...

Страница 23: ...ng terminals are used for connecting the call point 2 x Negative in terminals note if you only connect to the negative in terminals then the isolator is bypassed 1 x Positive in terminal 1 x Positive...

Страница 24: ...llows Terminal L1IN is ve Blue Terminal L2 is ve Brown These are the only two connections required Deep Base MKII CB D Common Base MKII CB 6 3 3 ZAI MI Input Module The end of line resistor value is 2...

Страница 25: ...er circuit is 10K When using the ZASC make sure the PSU being used has a fault output relay so that in the event of a power supply fault it is reported to the control panel Note All Power Supplies use...

Страница 26: ...l Connecting the sounder is done using the terminals in the back box of the device Please refer to the above diagram 6 3 8 Sandwich Sounder The sandwich sounder has no wiring to connect as it just cli...

Страница 27: ...ted version requires a standard detector base Each version of the remote LED can monitor 1 or up to 12 devices The way in which the LED is programmed is either via the DIP switches on the device or so...

Страница 28: ...TABLE ADDRESS SWITCHES ADDRESS SWITCHES ADDRESS SWITCHES 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 0 N O T U S E D 43 OFF OFF ON OFF ON OFF ON ON 86 ON OFF OFF ON OFF ON OFF ON 1 OFF ON ON ON O...

Страница 29: ...22 ON OFF ON OFF OFF OFF OFF ON 37 OFF ON OFF ON ON OFF ON ON 80 ON ON ON ON OFF ON OFF ON 123 OFF OFF ON OFF OFF OFF OFF ON 38 ON OFF OFF ON ON OFF ON ON 81 OFF ON ON ON OFF ON OFF ON 124 ON ON OFF O...

Страница 30: ...N ON OFF ON ON OFF OFF 244 ON ON OFF ON OFF OFF OFF OFF 159 OFF OFF OFF OFF OFF ON ON OFF 202 ON OFF ON OFF ON ON OFF OFF 245 OFF ON OFF ON OFF OFF OFF OFF 160 ON ON ON ON ON OFF ON OFF 203 OFF OFF ON...

Страница 31: ...t low power requirements 450mA max A separate power supply will be required for higher current applications 6 8 FIELD DEVICE TERMINATION S S ER R E Connect loop Earth Screens to Earth Bar Figure 7 Con...

Страница 32: ...onfiguration software But to enter it manually at the panel Turn the key switch clockwise to the Controls Enabled Position The controls Active LED will light Press any key followed by the level 2 pass...

Страница 33: ...m to always have your loop quality at 100 0 As the quality of communications decreases the chance of the system giving out false alarms or faults increases It can also cause the response from real eve...

Страница 34: ...is illustrates the command structure in a menu tree flowchart of the control keys 7 1 13 CONFIGURING THE LOOPS Turn the key switch clockwise to the Controls Enabled Position The controls Active LED wi...

Страница 35: ...cted according to its DIP switch setting The installation engineer must now assign a label or location for each device e g ROOM 107 A maximum of 20 characters can be used for each label At the same ti...

Страница 36: ...s This is also a good way of tracking down double addresses Turn the key switch clockwise to the Controls Enabled Position The controls Active LED will light Press any key followed by the level 2 pass...

Страница 37: ...only one node set as controller on the network Network Filter This determines whether this node reports all network events or just those from a specific network address Node search This should be perf...

Страница 38: ...in a master slave topology Multiple slaves can share the same bus but only one master can be in the line at the same time Master can communicate with a specific device peer to peer or with broadcast f...

Страница 39: ...FOR MORE INFORMATION ON USING THE MODBUS PLEASE REFER TO THE MODBUS REGISTERS MANUAL Doc No GLT 256 7 2 8 6 REPEATER PANEL The Repeater Panel is used to remotely indicate the status of all CIE s that...

Страница 40: ...apply to a detector alarm in Zone 1 and will ignore all other alarms in Zone 1 Multiple point alarm means that at least 2 points devices in Zone 1 must be activated before the programmed Effects occur...

Страница 41: ...nd outputs can be selected from 4 categories Point Zone Loop and Panel Example of Selecting a Logic Event New Logic The following example shows LOGIC No 2 top right of LCD being selected The Quatro is...

Страница 42: ...e DAY MODE will be active when the day mode is inactive the NIGHT mode will take over Once these settings have been selected press Next to confirm Select the zone range to have the two stage delays ap...

Страница 43: ...is same location by pressing Output and changing the delay time as required If a user needs to disable all current delays that are on the panel then this can be done by entering the User menu Delays D...

Страница 44: ...it to the required output Same with cause and affects you have the ability to change event type action settings add delays and to also tell the output device whether to active or shut down after a del...

Страница 45: ...ELECTION COMMENT Zones Show Displays zone details Show En Zones Indicates enabled zones Show Dis Zones Indicates disabled zones Show Test Zones Displays zones in test mode Enable Enables zones in rang...

Страница 46: ...er is fitted Toggling LED Activates LED selected point to locate devices on a loop Actions New Add a new cause effect action See Section 9 1 Modify Modify an existing Action New Logic Add a new logic...

Страница 47: ...date to print events from that date to present day Date Time Date xx xx xx Time xx xx Date Time Setup 10 3 CAUSE EFFECT TABLE ACTIONS NEW See also Section 9 1 Input Selection Input Type Selection 1 S...

Страница 48: ...user needs the rest of the system to continue running but doesn t want spurious false alarms The panel will respond in the usual manner to any events in any non disabled zones Any number of zones can...

Страница 49: ...y changes from SYSTEM NORMAL to DISABLED POINTS as shown In the example line 2 indicates that a total of 5 points have been disabled and the 1st of these is shown on line 3 The 1st disabled device is...

Страница 50: ...nd the Alarm sounders will operate for a further 10 seconds If an Alarm occurs on a zone that is not programmed to test the Fire Alarm Panel will continue to operate as normal 12 2 TO PROGRAMME ZONE I...

Страница 51: ...more devices This will cause the indicating LEDs for all devices with this address to flash Old Call Points Sounders and some I O units will not be indicated as they have no panel controlled LED to li...

Страница 52: ...placing 13 4 SUPPLY FAULTS LOSS OF BATTERY POWER OR LOW BATTERY VOLTAGE Check battery fuse Check that battery connections are secure Check battery voltage should be around 26 27V Check that the two ba...

Страница 53: ...T DISABLEMENTS FAULTS section of the panel 13 8 OUT OF SERVICE FAULTS If the system is in a condition in which it is unable to detect a fire or sound the alarm for example if a loop is being configure...

Страница 54: ...log see example For a general fault line 2 is simply a description of the fault and there is no information on line 3 The size of the Fault log is 1024 Test Log 512 This category indicates events tha...

Страница 55: ...48 Fyreye MKII Addressable Xtratone Sounder MKII AXT 0 65 N A 4 5 64 Fyreye MKII Addressable Xtratone Sounder Beacon MKII AXTB 2 3 N A 20 3 20 Fyreye MKII Addressable Xtratone Flasher MKII AXF 0 6 N A...

Страница 56: ...p Quatro panel with 80 Fyreye Extra Addressable Optical Smoke Detectors 15 Zeta Addressable Manual Call Points 20 Zeta Addressable Securetone 2 Sounders and the required standby is 24 hours It will ne...

Страница 57: ...Steel QT 3 SS Premier Quatro 4 Loop Analogue Addressable Fire Alarm Panel In Stainless Steel QT 4 SS Premier Quatro 1 Loop Analogue Addressable Fire Alarm Panel In Stainless Steel W Printer QT 1P SS P...

Страница 58: ...on 14 2 Mentioned 13 1 should have been 14 1 Added better explanation of selecting test mode with sounders 1 33 14 1 2013 Corrected EOL in sounder connection drawings from 10K to 4k7 1 34 14 8 2015 Re...

Страница 59: ...2002 A2 2006 EN54 4 1997 A1 2002 A2 2006 Control and indicating equipment for fire detection and fire alarm systems for buildings Premier Quatro QT 1 QT 2 QT 3 QT 4 Provided options Output to fire ala...

Отзывы: