RVZC30 (and BB/T/TBB/WA), RVZP30 (and BB/T/TBB/WA), RVC24
18
0407
Figure 17A: Refrigeration line sizing - Frozen Foods
R-404 Line Sizing Tables for Zero Zone VZ Frozen Food Freezer (-7°F Evaporator Temperature)
Liquid Line Sizing - Electric Defrost*
Up to 50 equivalent feet
Up to 100 equivalent feet
Up to 150 equivalent feet
Up to 200 equivalent feet
90°F Liquid, 2°F Pressure Drop
Δ
90°F Liquid, 2°F Pressure Drop
Δ
90°F Liquid, 2°F Pressure Drop
Δ
90°F Liquid, 2°F Pressure Drop
Δ
From
To
Liquid Line
From
To
Liquid Line
From
To
Liquid Line
From
To
Liquid Line
0
7,300
1/4
+
0
4,970
1/4
+
0
3,960
1/4
+
0
3,370
1/4
+
7,310
15,000
5/16
+
4,980
10,300
5/16
+
3,970
8,150
5/16
+
3,380
6,940
5/16
+
15,010
27,300
3/8
10,310
18,700
3/8
8,160
14,900
3/8
6,950
12,700
3/8
27,310
64,600
1/2
18,710
44,300
1/2
14,910
35,500
1/2
12,710
30,300
1/2
64,610 122,000
5/8
44,310
83,200
5/8
35,510
66,700
5/8
30,310
56,900
5/8
*
For hot gas defrost, use a liquid line one size larger than shown.
66,710 111,000
7/8
†
56,910
94,800
7/8
†
∆
For 1°F pressure drop, multiply rated Btuh by 1.45 before using the Liquid Line Sizing Table.
+
Larger liquid line size may be used (such as 3/8), if preferred.
†
3/4 liquid line may be used to reduce cost.
For rated Btuh:
For rated Btuh:
For rated Btuh:
For rated Btuh:
40°F
50°F
60°F
70°F
80°F
90°F
100°F
120°F
0.96
0.95
0.95
0.95
0.97
1.00
1.05
1.21
Liquid Correction Factors for Liquid Line Sizing Table - Use Maximum Liquid Temperature
For maximum liquid temperatures other than 90°F, multiply rated BTU by liquid correction factor before using the Liquid Line Sizing Table.
Maximum Liquid Temperature:
Liquid Correction Factor:
110°F
1.12
Suction Horizontal Line Sizing
Up to 50 equivalent feet
Up to 100 equivalent feet
Up to 150 equivalent feet
Up to 200 equivalent feet
90°F Liquid, 2°F Pressure Drop
‡
90°F Liquid, 2°F Pressure Drop
‡
90°F Liquid, 2°F Pressure Drop
‡
90°F Liquid, 2°F Pressure Drop
‡
From
To
Horizontal
From
To
Horizontal
From
To
Horizontal
From
To
Horizontal
0
1,730
3/8
++
0
1,180
3/8
++
0
940
3/8
++
0
800
3/8
++
1,740
4,100
1/2
++
1,190
2,810
1/2
++
950
2,240
1/2
++
810
1,910
1/2
++
4,110
7,700
5/8
++
2,820
5,280
5/8
++
2,250
4,220
5/8
++
1,920
3,600
5/8
++
7,710
12,800
7/8
†
5,290
8,780
7/8
†
4,230
7,030
7/8
†
3,610
6,000
7/8
†
12,810
20,300
7/8
8,790
14,000
7/8
7,040
11,200
7/8
6,010
9,530
7/8
20,310
41,000
1-1/8
14,010
28,200
1-1/8
11,210
22,700
1-1/8
9,540
19,400
1-1/8
41,010
71,400
1-3/8
28,210
49,200
1-3/8
22,710
39,500
1-3/8
19,410
33,800
1-3/8
71,410 113,000
1-5/8
49,210
77,800
1-5/8
39,510
62,500
1-5/8
33,810
53,500
1-5/8
62,510 130,000
2-1/8
53,510 112,000
2-1/8
‡
For 1°F pressure drop, multiply rated BTU by 1.44 before using the Suction Horizontal Line Sizing Table.
++
Larger suction horizontal line size may be used, if preferred.
†
3/4 horizontal suction line may be used to reduce cost.
For rated Btuh:
For rated Btuh:
For rated Btuh:
For rated Btuh:
40°F
50°F
60°F
70°F
80°F
90°F
100°F
120°F
0.72
0.76
0.81
0.86
0.92
1.00
1.09
1.37
Liquid Correction Factors for Suction Horizontal Line Sizing Table - Use Maximum Liquid Temperature
For maximum liquid temperatures other than 90°F, multiply rated BTU by liquid correction factor before using the Liquid Line Sizing Table.
Maximum Liquid Temperature:
Liquid Correction Factor:
110°F
1.21
Suction Vertical Riser Sizing
Maximum Allowable Riser Size For Adequate Oil Return*
70°F Minimum Liquid Temperature, using 0.35 PSI Per 100 Feet (per 2006 ASHRAE Handbook - Refrigeration).
For rated Btuh:
From
To
Vertical
1,360
2,550
1/2
2,560
4,270
5/8
4,280
6,790
5/8
†
6,800
13,900
7/8
13,910
24,300
1-1/8
24,310
38,400
1-3/8
38,410
80,000
1-5/8
80,010 142,000
2-1/8
*
If horizontal line size is smaller than specified vertical riser size, the smaller size may be used for both.
†
3/4 suction riser may be used to reduce pressure drop.
It may be necessary to make adjustments to compensate for
special situations which cause the actual Btuh to differ from
the rated Btuh of the cases.
All liquid line and suction line sizes are inches, refrigeration O.D.
Subject to change without notice.
Liquid Correction Factors for Suction Vertical Riser Sizing Table - Use Minimum Liquid Temperature
Multiply rated BTU by liquid correction factor before using the Suction Vertical Riser Sizing Table.
40°F
50°F
60°F
70°F
80°F
90°F
100°F
0.84
0.88
0.94
1.00
1.07
1.16
1.27
CCR, 4/4/07
Minimum Liquid Temperature:
Liquid Correction Factor:
SP-0612-01, Rev A
Содержание RVZC30
Страница 1: ......
Страница 2: ...RVZC30 and BB T TBB WA RVZP30 and BB T TBB WA RVC24 2 0407...
Страница 5: ...RVZC30 and BB T TBB WA RVZP30 and BB T TBB WA RVC24 5 0407 Figure 1 Case label information...
Страница 9: ...RVZC30 and BB T TBB WA RVZP30 and BB T TBB WA RVC24 9 0407 Figure 5B All base locations...
Страница 10: ...RVZC30 and BB T TBB WA RVZP30 and BB T TBB WA RVC24 10 0407 Figure 5C All base locations...
Страница 22: ...RVZC30 and BB T TBB WA RVZP30 and BB T TBB WA RVC24 22 0407 Figure 21 Electric defrost 30 wiring...
Страница 23: ...RVZC30 and BB T TBB WA RVZP30 and BB T TBB WA RVC24 23 0407 Figure 22 Electric defrost 24 wiring...
Страница 24: ...RVZC30 and BB T TBB WA RVZP30 and BB T TBB WA RVC24 24 0407 Figure 23 Hot gas wiring...
Страница 25: ...RVZC30 and BB T TBB WA RVZP30 and BB T TBB WA RVC24 25 0407 Figure 24 Single point wiring...
Страница 26: ...RVZC30 and BB T TBB WA RVZP30 and BB T TBB WA RVC24 26 0407 Figure 25 Master satellite wiring...
Страница 29: ...RVZC30 and BB T TBB WA RVZP30 and BB T TBB WA RVC24 29 0407 Figure 27 24 Electric Figure 26 30 Electric...
Страница 30: ...RVZC30 and BB T TBB WA RVZP30 and BB T TBB WA RVC24 30 0407 Figure 28 Coil 30 Hot gas Figure 29 Coil 24 Hot gas...