![Zennio ZVI-SQTMDD Скачать руководство пользователя страница 67](http://html1.mh-extra.com/html/zennio/zvi-sqtmdd/zvi-sqtmdd_user-manual_3438534067.webp)
Square TMD-Display
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
67
2.4.2
DISABLED
While a display zone remains disabled, it does not represent anything and cannot be
linked to any button – it will remain empty.
ETS PARAMETERISATION
This function has no related parameters.
2.4.3
SINGLE
Single boxes have a size of 64 x 32 pixels. The display can be divided into up to four
single boxes.
Single boxes can be assigned the following types of indicators:
Icon
: the indicator will represent an icon according to the value of an object.
Depending on the type of object there are two types of icons:
One bit: an icon represents the On state and another one represents the
Off state.
Enumeration: up to six different states can be represented through one
icon each.
Number
: the indicator will represent a number (received through the
associated object) and a three-character text representing the units. Different
number types are available for the different object types: Scaling, Counter (1
byte unsigned), Counter (1 byte signed), Counter (2 bytes unsigned), Counter
(2 bytes signed), Counter (4 bytes unsigned), Float (2 bytes).
Text
: the indicator will represent a text according to the value of an object.
This indicator is totally analogous to the Icon indicator, but each value is
associated to a text instead of an icon. The types are the same:
One bit: a text represents the On state and another one represents the Off
state.
Enumeration: up to six different states can be represented through one
text each.