MCC
http://www.zennio.com
Technical Support:
http://support.zennio.com
22
15, 82, 149, 216, 283, 350, 417, 484,
551, 618, 685, 752, 819
1 Bit
O
C T R -
-
DPT_Heat_Cool
0/1
[HTx] [A] Mode Status
0 = Cooling; 1 = Heating
16, 83, 150, 217, 284, 351, 418, 485,
552, 619, 686, 753, 820
1 Byte
I
C T - W
U
DPT_Scaling
0% - 100%
[HTx] [A] Fan Speed
0% - 100%
17, 84, 151, 218, 285, 352, 419, 486,
553, 620, 687, 754, 821
1 Bit
I
C T - W
U
DPT_Switch
0/1
[HTx] [A] Fan: Manual/Automatic
0 = Manual; 1 = Automatic
1 Bit
I
C T - W
U
DPT_Switch
0/1
[HTx] [A] Fan: Manual/Automatic
0 = Automatic; 1 = Manual
18, 85, 152, 219, 286, 353, 420, 487,
554, 621, 688, 755, 822
1 Bit
O
C T R -
-
DPT_Switch
0/1
[HTx] [A] On/Off Fancoil
0 = Off; 1 = On
19, 86, 153, 220, 287, 354, 421, 488,
555, 622, 689, 756, 823
1 Bit
I
C - - W
-
DPT_Reset
0/1
[HTx] [B] User Comfort Setpoint Reset
0 = Nothing; 1 = Reset
20, 87, 154, 221, 288, 355, 422, 489,
556, 623, 690, 757, 824
2
Bytes
I
C T - W
U
DPT_Value_Temp
-273.00° -
670760.00°
[HTx] [B] User Setpoint Control
(Cooling and Heating)
[-20°C, 100°C]
2
Bytes
I
C T - W
U
DPT_Value_Tempd
-670760.00° -
670760.00°
[HTx] [B] User Setpoint Offset (Cooling
and Heating)
[-15°C, 15°C]
21, 88, 155, 222, 289, 356, 423, 490,
557, 624, 691, 758, 825
2
Bytes
I/O
C T R W
U
DPT_Value_Temp
-273.00° -
670760.00°
[HTx] [B] Comfort Setpoint (Cooling)
[-20°C, 100°C]
22, 89, 156, 223, 290, 357, 424, 491,
558, 625, 692, 759, 826
2
Bytes
I/O
C T R W
U
DPT_Value_Temp
-273.00° -
670760.00°
[HTx] [B] Standby Setpoint (Cooling)
[-20°C, 100°C]
23, 90, 157, 224, 291, 358, 425, 492,
559, 626, 693, 760, 827
2
Bytes
I/O
C T R W
U
DPT_Value_Temp
-273.00° -
670760.00°
[HTx] [B] Economy Setpoint (Cooling)
[-20°C, 100°C]
24, 91, 158, 225, 292, 359, 426, 493,
560, 627, 694, 761, 828
2
Bytes
I/O
C T R W
U
DPT_Value_Temp
-273.00° -
670760.00°
[HTx] [B] Protection Setpoint (Cooling)
[-20°C, 100°C]
25, 92, 159, 226, 293, 360, 427, 494,
561, 628, 695, 762, 829
2
Bytes
I/O
C T R W
U
DPT_Value_Temp
-273.00° -
670760.00°
[HTx] [B] Comfort Setpoint (Heating)
[-20°C, 100°C]
26, 93, 160, 227, 294, 361, 428, 495,
562, 629, 696, 763, 830
2
Bytes
I/O
C T R W
U
DPT_Value_Temp
-273.00° -
670760.00°
[HTx] [B] Standby Setpoint (Heating)
[-20°C, 100°C]
27, 94, 161, 228, 295, 362, 429, 496,
563, 630, 697, 764, 831
2
Bytes
I/O
C T R W
U
DPT_Value_Temp
-273.00° -
670760.00°
[HTx] [B] Economy Setpoint (Heating)
[-20°C, 100°C]
28, 95, 162, 229, 296, 363, 430, 497,
564, 631, 698, 765, 832
2
Bytes
I/O
C T R W
U
DPT_Value_Temp
-273.00° -
670760.00°
[HTx] [B] Protection Setpoint (Heating)
[-20°C, 100°C]
29, 96, 163, 230, 297, 364, 431, 498,
565, 632, 699, 766, 833
2
Bytes
O
C T R -
-
DPT_Value_Temp
-273.00° -
670760.00°
[HTx] [B] Real Setpoint Status
[-20°C, 100°C]
30, 97, 164, 231, 298, 365, 432, 499,
566, 633, 700, 767, 834
2
Bytes
O
C T R -
-
DPT_Value_Temp
-273.00° -
670760.00°
[HTx] [B] User Setpoint Status
[-20°C, 100°C]
2
Bytes
O
C T R -
-
DPT_Value_Tempd
-670760.00° -
670760.00°
[HTx] [B] User Setpoint Offset Status
[-15°C, 15°C]
31, 98, 165, 232, 299, 366, 433, 500,
567, 634, 701, 768, 835
2
Bytes
I/O
C T R W
U
DPT_TimePeriodSec
0 - 65535
[HTx] [C] Transition Time: Comfort to
Default Mode
Seconds (0 = Disabled)
2
Bytes
I/O
C T R W
U
DPT_TimePeriodMin
0 - 65535
[HTx] [C] Transition Time: Comfort to
Default Mode
Minutes (0 = Disabled)