![Zennio ZCL-MCC Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/zennio/zcl-mcc/zcl-mcc_user-manual_3464852025.webp)
MCC
http://www.zennio.com
Technical Support:
http://support.zennio.com
25
56, 123, 190, 257, 324, 391, 458, 525,
592, 659, 726, 793, 860
2
Bytes
I/O
C T R W
U
DPT_Value_Temp
-273.00° -
670760.00°
[HTx] [D] Eco Mode: Lower Limit
(Cooling)
Lower Value for the Ecological Range
57, 124, 191, 258, 325, 392, 459, 526,
593, 660, 727, 794, 861
2
Bytes
I/O
C T R W
U
DPT_Value_Temp
-273.00° -
670760.00°
[HTx] [D] Eco Mode: Upper Limit
(Heating)
Upper Value for the Ecological Range
58, 125, 192, 259, 326, 393, 460, 527,
594, 661, 728, 795, 862
2
Bytes
O
C T R -
-
DPT_Value_Temp
-273.00° -
670760.00°
[HTx] [D] Setpoint to Split
[-20°C, 100°C]
59, 126, 193, 260, 327, 394, 461, 528,
595, 662, 729, 796, 863
2
Bytes
I
C - - W
-
DPT_Value_Humidity
-671088.64 -
670760.96
[HTx] [F] Current Humidity
Humidity Sensor Value
60, 127, 194, 261, 328, 395, 462, 529,
596, 663, 730, 797, 864
2
Bytes
I/O
C T R W
U
DPT_Value_Humidity
-671088.64 -
670760.96
[HTx] [F] High Humidity Alarm
Threshold
Value of High Humidity Alarm
Threshold
61, 128, 195, 262, 329, 396, 463, 530,
597, 664, 731, 798, 865
1 Bit
I/O
C T R W
U
DPT_Enable
0/1
[HTx] [F] Dehumidification Control
0 = Disabled; 1 = Enabled
62, 129, 196, 263, 330, 397, 464, 531,
598, 665, 732, 799, 866
1 Bit
O
C T R -
-
DPT_Bool
0/1
[HTx] [F] Dehumidification Status
0 = No Dehumidifying; 1 =
Dehumidifying
63, 130, 197, 264, 331, 398, 465, 532,
599, 666, 733, 800, 867
1 Bit
O
C T R -
-
DPT_Alarm
0/1
[HTx] [F] High Humidity
0 = No Alarm; 1 = Alarm
64, 131, 198, 265, 332, 399, 466, 533,
600, 667, 734, 801, 868
1 Bit
I/O
C T R W
U
DPT_Enable
0/1
[HTx] [F] Enable Apparent
Temperature
0 = Room Temperature; 1 =
Apparent Temperature
65, 132, 199, 266, 333, 400, 467, 534,
601, 668, 735, 802, 869
1 Byte
O
C T R -
-
DPT_Scaling
0% - 100%
[HTx] [Cooling] Control Variable
PI Control (Continuous)
66, 133, 200, 267, 334, 401, 468, 535,
602, 669, 736, 803, 870
1 Byte
O
C T R -
-
DPT_Scaling
0% - 100%
[HTx] [Heating] Control Variable
PI Control (Continuous)
67, 134, 201, 268, 335, 402, 469, 536,
603, 670, 737, 804, 871
1 Bit
O
C T R -
-
DPT_Switch
0/1
[HTx] [Cooling] Control Variable
2-Point Control
1 Bit
O
C T R -
-
DPT_Switch
0/1
[HTx] [Cooling] Control Variable
PI Control (PWM)
68, 135, 202, 269, 336, 403, 470, 537,
604, 671, 738, 805, 872
1 Bit
O
C T R -
-
DPT_Switch
0/1
[HTx] [Heating] Control Variable
2-Point Control
1 Bit
O
C T R -
-
DPT_Switch
0/1
[HTx] [Heating] Control Variable
PI Control (PWM)
69, 136, 203, 270, 337, 404, 471, 538,
605, 672, 739, 806, 873
1 Bit
O
C T R -
-
DPT_Switch
0/1
[HTx] [Cooling] Additional Cool
Temp >= (SBand) => "1"
70, 137, 204, 271, 338, 405, 472, 539,
606, 673, 740, 807, 874
1 Bit
O
C T R -
-
DPT_Switch
0/1
[HTx] [Heating] Additional Heat
Temp <= (Setpoint-Band) => "1"
71, 138, 205, 272, 339, 406, 473, 540,
607, 674, 741, 808, 875
1 Bit
O
C T R -
-
DPT_Switch
0/1
[HTx] [Cooling] PI State
0 = PI Signal 0%; 1 = PI Signal
Greater than 0%
72, 139, 206, 273, 340, 407, 474, 541,
608, 675, 742, 809, 876
1 Bit
O
C T R -
-
DPT_Switch
0/1
[HTx] [Heating] PI State
0 = PI Signal 0%; 1 = PI Signal