MCC
http://www.zennio.com
Technical Support:
http://support.zennio.com
12
Comfort Lower Limit
Comfort Upper Limit
Hidden Offset Value
Eco Mode: Lower Limit (Cooling)
Eco Mode: Upper Limit (Heating)
High Humidity Alarm Threshold
Dehumidification Control
Enable Apparent Temperature
These requests only apply to the enabled thermostats and to the linked objects.
Notes
:
These read requests are sent gradually, to prevent the saturation of the KNX
bus
.
To obtain the expected behaviour, the communication objects that are read-
requested must have the Writing, Transmission and Update flags
enabled
.
If a role change occurs while performing the read requests, the remaining
responses will not be affected, as they will be sent as if the role change had
not taken place.
2.2.2.2
OBJECT COMMUNICATION NOTIFICATIONS
Periodically (time set by parameter), the slave device sends
a ‘1’ through the slave
notification communication object.
The reception of any value through the slave notification object will be ignored.
2.2.2.3
MASTER FAILURE DETECTION
In the slave role, the device permanently listens for the master notifications. After
two
and a half times
the transmission time without receiving any master notification,
the
slave device switches to the master role and notifies it by sending a “1” through