Timer Type
[
1-Bit Value
/ Scene
]: allows the user to select how the timer will be
controlled.
Scene Number
[
1
…64
]
: shown only after selecting “
Scene
” for the above
parameter. This field defines the number of the scene that will be sent to the
bus on the execution of the timed sending.
Enablement
[
0 = Disable; 1 = Enable
/ 0 = Enable; 1 = Disable
]: sets the value
to enable and disable the timer through the object
“
[Pn][Bi] Daily Timer
Enabling
”
.
3.3.2.5.4
Weekly Timer
Boxes configured as weekly timers let the final user program a timed sending of a binary
or scene value to the bus (according to the parameterisation) at a certain time on certain
days (on a weekly basis).
The difference between the daily and the weekly timers is that the latter does not permit
the countdown-based sending, although it does permit that a time-based sending takes
place every week, on the days selected by the user
Hence, when the user presses on the box, a window similar to Figure 65 will pop up.
Figure 65.
W eekly Timer Pop-up.
This window contains the following elements:
Day Selector: lets the user select the days the timed sending will take place on.
The first day of the week depends on the parameterisation of the GENERAL tab