MINiBOX 45 v2/MINiBOX 25 v2

 

http://www.zennio.com

 

              

Technical Support:

 

http://support.zennio.com

 

 

1.2

 

INSTALLATION 

MINiBOX 45 / 25 v2 connects to the KNX bus through the on-board KNX connector.  

Once the device is provided with power from the KNX bus, both the individual address 

and the associated application program may be downloaded. 

This  device  does  not  need  any  additional  external  power  since  it  is  entirely  powered 

through the KNX bus. 

 

 

 

 

 

 

Figure 1. 

MINiBOX 45 v2. Elements 

Note

the  above  element  diagram  is  slightly  different  for  MINiBOX  25  v2,  although 

entirely analogous

The main elements of the device are described next. 

 

Test/Prog. Pushbutton (6)

: a short press on this button sets the device into 

the programming mode, making the associated LED (5) light in red.  

Note

if  this  button  is  held  while  plugging  the  device  into  the  KNX  bus,  the 

device will enter into safe mode. In such case, the LED will blink in red every 

0.5 seconds.

 

 

Outputs (7)

: output ports for the insertion of the stripped cables of the systems 

being  controlled  by  the  actuator  (see  section  2.3).  Please  secure  the 

connection by means of the on-board screws. 

1. 

Output Control Pushbutton. 

2. 

Output LED Indicator. 

3. 

Analogue-Digital Inputs. 

4. 

KNX Bus Connector. 

5. 

Prog./Test LED.   

6. 

Prog./Test Pushbutton. 

7. 

Relay Outputs. 

Содержание MINiBOX 45v2

Страница 1: ...MINiBOX 45 v2 MINiBOX 25 v2 Multifunction Actuator with 4 or 5 Outputs and 5 Inputs ZIOMN45V2 USER MANUAL ZIOMN25V2 Application program version 1 1 User manual edition 1 1 _a www zennio com...

Страница 2: ...2 MINiBOX 45 v2 4 1 2 Installation 6 1 3 Start Up and Power Loss 7 2 Configuration 8 2 1 General 8 2 2 Inputs 11 2 2 1 Binary Input 11 2 2 2 Temperature Probe 11 2 2 3 Motion Detector 11 2 3 Outputs 1...

Страница 3: ...45 v2 MINiBOX 25 v2 http www zennio com Technical Support http support zennio com 3 DOCUMENT UPDATES Version Changes Page s 1 1_a Changes in the application program of MINiBOX 45 25 v2 Internal optim...

Страница 4: ...e as Up to 4 2 individual ON OFF output Up to 2 1 independent shutter channels with or without slats Up to 1 two pipe fan coil modules where both the fan speed control and the valve control are perfor...

Страница 5: ...p www zennio com Technical Support http support zennio com 5 Manual operation supervision of the 2 or 4 relay outputs through the on board pushbuttons and LEDs Heartbeat or periodical still alive noti...

Страница 6: ...although entirely analogous The main elements of the device are described next Test Prog Pushbutton 6 a short press on this button sets the device into the programming mode making the associated LED 5...

Страница 7: ...zennio com 1 3 START UP AND POWER LOSS During the start up of the device the Test Prog LED will blink in blue colour for a few seconds before the device is ready External orders will not be executed...

Страница 8: ...e is General From this screen it is possible to activate deactivate all the required functionality Figure 2 Default screen Inputs disabled enabled 1 enables o disables the Inputs tab on the left menu...

Страница 9: ...r more details Sending of Indication Objects 0 and 1 on Bus Voltage Recovery disabled enabled this parameter lets the integrator activate two new communication objects Reset 0 and Reset 1 which will b...

Страница 10: ...of up to 255 seconds to prevent bus overload The following sendings match the period set Show Relay Switches Counter Objects disabled enabled enables two communication objects to keep track of the nu...

Страница 11: ...ual Binary Inputs available in the MINiBOX 45 25 v2 product section at the Zennio website www zennio com 2 2 2 TEMPERATURE PROBE Please refer to the specific user manual Temperature Probe available in...

Страница 12: ...cally to the corresponding product section to obtain the aforementioned document Motion detectors with references ZN1IO DETEC and ZN1IO DETEC N are not compatible with MINiBOX 45 25 v2 may report inac...

Страница 13: ...ndent shutter channels respectively Fan Coil modules which allow the control of the fan and the valve of two pipe fan coil units it is possible to control one independent fancoil block only in MINiBOX...

Страница 14: ...execution of each function can depend on a configurable condition which will be evaluated every time the function is triggered through specific parameterizable communication objects The result after...

Страница 15: ...v2 implements four Zennio thermostats which can be enabled and configured independently Please refer to the specific Zennio Thermostat user manual available in the MINiBOX 45 25 v2 product section at...

Страница 16: ...r order a thermostat setpoint or mode switch order a constant value a scene Only the trigger object and the twelve status objects are required to be binary on off The most typical scenario for this Ma...

Страница 17: ...f the above state objects with such value Otherwise i e if none of them has a value of 1 it will be sent with a value of 0 Trigger Value 0 1 0 1 sets the value that will trigger when received through...

Страница 18: ...HVAC thermostat mode value configurable in Value Auto Comfort Standby Economy Building Protection whenever the general switch off takes off Note the above options are not mutually exclusive it is pos...

Страница 19: ...for that output or that channel such temporisation will be interrupted and only the delay and the action of the new scene will be executed ETS PARAMETERISATION Prior to setting the scene temporisation...

Страница 20: ...coil module Note In the configuration of a scene of an output shutter channel fan coil it is possible to parameterize several scenes with the same scene number This means that several delay parameters...

Страница 21: ...y switching to the Test On mode unless disabled by parameter needs to be done by long pressing the Prog Test button for at least three seconds until the LED is no longer red and turns yellow From that...

Страница 22: ...vement up down depending on the button pressed will take place The status objects will be sent to the bus when corresponding Fan Coil module the behaviour will depend on whether a fan labelled or a va...

Страница 23: ...ding on whether the output has been parameterised as an individual output as part of a shutter channel or a fan coil block the reactions to the button presses will differ Individual output short or lo...

Страница 24: ...tatus is carried out when exiting this mode so that any change in the alarm status or blocking of the outputs while Test ON mode is active is taken into account when exiting this mode and is updated w...

Страница 25: ...nabled object Manual Control Lock turns visible as well as two more parameters Value 0 Lock 1 Unlock 0 Unlock 1 Lock defines whether the manual control lock unlock should take place respectively upon...

Страница 26: ...x Temperature Source 1 External Sensor Temperature 7 45 83 121 2 Bytes I C W DPT_Value_Temp 273 00 670760 00 Tx Temperature Source 2 External Sensor Temperature 8 46 84 122 2 Bytes O C T R DPT_Value_T...

Страница 27: ...O C R W DPT_Switch 0 1 Tx Main System Cool 0 System 1 1 System 2 29 67 105 143 1 Bit I O C R W DPT_Switch 0 1 Tx Main System Heat 0 System 1 1 System 2 30 68 106 144 1 Bit I C W DPT_Enable 0 1 Tx Ena...

Страница 28: ...ilding Protection ML Courtesy Switch On HVAC mode Auto Comfort Standby Economy Building Protection 180 184 188 192 196 2 Bytes O C T R DPT_Value_Temp 273 00 670760 00 Ix Current Temperature Temperatur...

Страница 29: ...8 191 Ix Short Press Run Scene Sending of 0 63 1 Byte C T DPT_SceneControl 0 63 128 191 Ix Short Press Save Scene Sending of 128 191 1 Bit I O C T R W DPT_Switch 0 1 Ix Switch Sensor Edge Sending of 0...

Страница 30: ...ress Darker Long Pr Darker Release Stop 4 Bit C T DPT_Control_Dimming 0x0 Stop 0x1 Dec by 100 0x7 Dec by 1 0x8 Stop 0xD Inc by 100 0xF Inc by 1 Ix Long Press Brighter Darker Long Pr Brighter Darker Re...

Страница 31: ...on Ix Presence State HVAC Auto Comfort Standby Economy Building Protection 247 276 305 334 363 1 Bit O C T R DPT_Occupancy 0 1 Ix Presence State Binary Binary Value 1 Bit O C T R DPT_Ack 0 1 Ix Presen...

Страница 32: ...Bit I C W DPT_Enable 0 1 Ox Lock 0 Unlock 1 Lock 420 431 442 453 1 Bit I C W DPT_Start 0 1 Ox Timer 0 Switch Off 1 Switch On 421 432 443 454 1 Bit I C W DPT_Start 0 1 Ox Flashing 0 Stop 1 Start 422 43...

Страница 33: ...1 Cx Sunshine Shadow 0 Shadow 1 Sunshine 501 529 1 Bit I C T W U DPT_Heat_Cool 0 1 Cx Cooling Heating 0 Heating 1 Cooling 1 Bit I C T W U DPT_Heat_Cool 0 1 Cx Cooling Heating 0 Cooling 1 Heating 502 5...

Страница 34: ...trol S0 0 S1 1 584 1 Byte O C T R DPT_Value_1_Ucount 0 255 FCx Fan Speed Enumeration Status S0 0 S1 1 S2 2 S3 3 1 Byte O C T R DPT_Value_1_Ucount 0 255 FCx Fan Speed Enumeration Status S0 0 S1 1 S2 2...

Страница 35: ...Bit O C T R DPT_Bool 0 1 FCx Control Value Error 0 No Error 1 Error 598 2 Bytes I C W U DPT_Value_Temp 273 00 670760 00 FCx Ambient Temperature Ambient Temperature 599 2 Bytes I C W U DPT_Value_Temp 2...

Страница 36: ...2147483648 2147483647 LF Function x Result 4 Byte Signed 1 Byte O C T R DPT_Scaling 0 100 LF Function x Result 1 Byte Percentage 2 Bytes O C T R DPT_Value_2_Count 32768 32767 LF Function x Result 2 By...

Страница 37: ...n and send us your inquiries about Zennio devices http support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio c...

Отзывы: