MINiBOX 45 v2/MINiBOX 25 v2
Technical Support:
26
ANNEX I. COMMUNICATION OBJECTS
“Functional range
” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a
particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
Note
:
objects referring to outputs 3 and 4 and a fan coil block are not available in MINiBOX 25 v2
.
Number
Size
I/O
Flags
Data type (DPT)
Functional Range
Name
Function
1
1 Bit
C T - - -
DPT_Trigger
0/1
Reset 0
Voltage Recovery -> Sending of 0
2
1 Bit
C T - - -
DPT_Trigger
0/1
Reset 1
Voltage Recovery -> Sending of 1
3
1 Bit
I
C - - W -
DPT_Enable
0/1
Lock Manual Control
0 = Lock; 1 = Unlock
1 Bit
I
C - - W -
DPT_Enable
0/1
Lock Manual Control
0 = Unlock; 1 = Lock
4
1 Bit
C T - - -
DPT_Trigger
0/1
[Heartbeat] Object to Send '1'
Sending of '1' Periodically
5
1 Byte
I
C - - W -
DPT_SceneControl
0-63; 128-191
[Thermostat] Scene Input
Scene Value
6, 44, 82, 120
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00° - 670760.00°
[Tx] Temperature Source 1
External Sensor Temperature
7, 45, 83, 121
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00° - 670760.00°
[Tx] Temperature Source 2
External Sensor Temperature
8, 46, 84, 122
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00° - 670760.00°
[Tx] Effective Temperature
Effective Control Temperature
9, 47, 85, 123
1 Byte
I
C - - W -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building Protection
[Tx] Special Mode
1-Byte HVAC Mode
10, 48, 86, 124
1 Bit
I
C - - W -
DPT_Ack
0/1
[Tx] Special Mode: Comfort
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: Comfort
0 = Off; 1 = On
11, 49, 87, 125
1 Bit
I
C - - W -
DPT_Ack
0/1
[Tx] Special Mode: Standby
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: Standby
0 = Off; 1 = On
12, 50, 88, 126
1 Bit
I
C - - W -
DPT_Ack
0/1
[Tx] Special Mode: Economy
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: Economy
0 = Off; 1 = On
13, 51, 89, 127
1 Bit
I
C - - W -
DPT_Ack
0/1
[Tx] Special Mode: Protection
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: Protection
0 = Off; 1 = On
14, 52, 90, 128
1 Bit
I
C - - W -
DPT_Window_Door
0/1
[Tx] Window Status (Input)
0 = Closed; 1 = Open
15, 53, 91, 129
1 Bit
I
C - - W -
DPT_Ack
0/1
[Tx] Comfort Prolongation
0 = Nothing; 1 = Timed Comfort
16, 54, 92, 130
1 Byte
O
C T R - -
DPT_HVACMode
1=Comfort
2=Standby
[Tx] Special Mode Status
1-Byte HVAC Mode