background image

 

 

 

MAXinBOX Hospitality

 

http://www.zennio.com

 

                 

Technical Support:

 

http://support.zennio.com

 

 

2

 

CONFIGURATION 

2.1

 

GENERAL 

After importing the corresponding database in ETS and adding the device into the 

topology  of  the  desired  project,  the  configuration  process  begins  by  entering  the 

Parameters tab of the device. 

ETS PARAMETERISATION 

From  the  “General”  tab  it  is  possible  to  mark/unmark  the  appropriate  checkboxes  to 

enable the  required functionality.  The only  one  active  by default  is  “

Manual  Control

” 

(see section 2.7), thus the corresponding tab will also be available from the beginning 

in the tab tree on the left. 

 

 

 

Figure 2 

General screen

 

  Once  activated,

  Inputs,  Binary  Outputs,  Fan  Coil,  Logical  Functions,

 

Manual Control 

(enabled by default) and 

Master Light

 bring additional tabs 

to  the  menu  on  the  left.  These  functions  and  their  parameters  will  be 

explained in later sections of this document.

 

 

Sending  of  Indication  Objects  (0  and  1)  on  Bus  Voltage  Recovery

:  this 

parameter lets the integrator activate 

two new communication objects (“

Reset 

0

” and “

Reset 1

”), which will be sent to the KNX bus with values “0” and “1” 

respectively whenever the device begins operation (for  example, after a bus 

Содержание MAXinBOX Hospitality ZCL-HP126

Страница 1: ...XinBOX Hospitality Two Four Pipe Fan Coil Controller with Two Digital Outputs and 6 Analogue Digital Inputs USER MANUAL ZCL HP126 Application program version 2 3 User manual edition 2 3 _a www zennio...

Страница 2: ...5 1 3 Start Up and Power Loss 6 1 4 Status Indicators 7 1 4 1 Binary and Shutter Outputs 7 1 4 2 Fan Coil Control Outputs Valve Fan 7 2 Configuration 8 2 1 General 8 2 2 Inputs 10 2 2 1 Binary Input...

Страница 3: ...lication program Inclusion of the Heartbeat module Inclusion of the Shutter Blind control module Update of the Logic Functions Master Light Control and Motion Detector modules 2 0 _a Changes in the ap...

Страница 4: ...are used to control the valve 2 relay outputs to control one three point valve or up to two on off valves One of these outputs can also be configured as an additional multi purpose relay output in thi...

Страница 5: ...ushbutton 9 a short press on this button sets the device into the programming mode making the associated LED 8 light in red Note if this button is held while plugging the device into the KNX bus the d...

Страница 6: ...iginal package of the device and also available at www zennio com 1 3 START UP AND POWER LOSS During the device start up the Prog Test LED will blink in blue colour for a few seconds before MAXinBOX H...

Страница 7: ...control outputs the LED indicator of each output will behave analogously as the LEDs of the binary outputs it will remain off while the corresponding valve is closed and on while the corresponding va...

Страница 8: ...Control see section 2 7 thus the corresponding tab will also be available from the beginning in the tab tree on the left Figure 2 General screen Once activated Inputs Binary Outputs Fan Coil Logical...

Страница 9: ...cation lets the integrator incorporate a one bit object to the project Heartbeat Object to Send 1 that will be sent periodically with value 1 to notify that the device is still working still alive Fig...

Страница 10: ...ilable under the MAXinBOX Hospitality product section at www zennio com 2 2 2 TEMPERATURE PROBE Please refer to the Temperature Probe user manual available under the MAXinBOX Hospitality product secti...

Страница 11: ...ding on the device it is actually being connected to the functionality may differ slightly Therefore please refer specifically to the aforementioned user manual Motion detectors with references ZN1IO...

Страница 12: ...ve loads PARAMETERISATION When the Outputs function has been activated in the General parameter screen the Outputs section will be available in the tree on the left containing itself a tab named Confi...

Страница 13: ...elays distribution for the valves control is shown in the following table for every possible parameterisation Number of pipes Valve type Output Action 4 On Off Output V1 Cooling Valve Output V2 Heatin...

Страница 14: ...bytes The execution of each function can depend on a configurable condition which will be evaluated every time the function is triggered through specific parameterisable communication objects The resu...

Страница 15: ...up to the integrator the decision of what to send to the KNX bus in both cases a shutter order a thermostat setpoint or mode switch order a constant value a scene Only the trigger object and the twel...

Страница 16: ...ue 0 1 or 0 1 being the latter the default option that will trigger when received through ML Trigger the master action the general switch off or the courtesy switch on General Switch Off Delay defines...

Страница 17: ...ailable here are entirely analogous to those already mentioned for General Switch Off However in this case the names of the objects start with ML Courtesy Switch On On the other hand sending scene sav...

Страница 18: ...tality independently for the relay outputs binary or shutter and for the fan coil outputs valves and fan The Test Off mode will be active unless it has been disabled by parameter after a download or a...

Страница 19: ...ngth of the button press and to the current state A long press makes the shutter start moving upwards or downwards depending on the button being pressed The LED will light in green until the end of th...

Страница 20: ...d fan speed is other than zero A switch off of the fan it is found to be in motion and the valve closes provided that the current mode is Heating under Cooling the fan will remain as is Disabled outpu...

Страница 21: ...ease or decrease of the fan speed depending on the button pressed In case the fan coil module is disabled in parameters it will work as non cyclical and through relay switching with a 0 3 s delay In a...

Страница 22: ...est On or both modes Note that as stated before using the Test Off mode does not require any special action while switching to the Test On mode does require long pressing the Prog Test button Lock Man...

Страница 23: ...mperature Temperature Sensor Value 6 10 14 18 22 26 1 Bit O C T R DPT_Alarm 0 1 Ix Overcooling 0 No Alarm 1 Alarm 7 11 15 19 23 27 1 Bit O C T R DPT_Alarm 0 1 Ix Overheating 0 No Alarm 1 Alarm 8 12 16...

Страница 24: ...un Scene Sending of 0 63 1 Byte C T DPT_SceneControl 0 63 128 191 Ix Short Press Save Scene Sending of 128 191 1 Bit I O C T R W DPT_Switch 0 1 Ix Switch Sensor Edge Sending of 0 or 1 1 Byte C T DPT_V...

Страница 25: ...righter Long Pr Brighter Release Stop 4 Bit C T DPT_Control_Dimming 0x0 Stop 0x1 Dec by 100 0x7 Dec by 1 0x8 Stop 0xD Inc by 100 0xF Inc by 1 Ix Long Press Darker Long Pr Darker Release Stop 4 Bit C T...

Страница 26: ...rcuit Error 0 No Error 1 Short Circuit Error 70 99 128 157 186 215 1 Byte O C T R DPT_Scaling 0 100 Ix Presence State Scaling 0 100 71 100 129 158 187 216 1 Byte O C T R DPT_HVACMode 1 Comfort 2 Stand...

Страница 27: ...ection 241 252 263 1 Byte I C W DPT_SceneControl 0 63 128 191 Ox Scenes 0 63 Execute 1 64 128 191 Save 1 64 242 253 264 1 Bit I C W DPT_BinaryValue 0 1 Ox On Off N O 0 Open Relay 1 Close Relay 1 Bit I...

Страница 28: ...ise 288 1 Bit I C W DPT_Ack 0 1 Cx Direct Positioning 0 No Action 1 Go to Position 289 1 Bit I C W DPT_Ack 0 1 Cx Direct Positioning 2 0 No Action 1 Go to Position 290 1 Bit I C W DPT_Ack 0 1 Cx Direc...

Страница 29: ...d 0 0 Off 1 On 383 1 Bit I C W U DPT_Switch 0 1 FC Manual Fan Speed 1 0 Off 1 On 384 1 Bit I C W U DPT_Switch 0 1 FC Manual Fan Speed 2 0 Off 1 On 385 1 Bit I C W U DPT_Switch 0 1 FC Manual Fan Speed...

Страница 30: ...itch 0 1 FC Cooling Valve Status 0 Closed 1 Open 1 Bit O C T R DPT_OpenClose 0 1 FC Valve Status 0 Open 1 Closed 1 Bit O C T R DPT_Switch 0 1 FC Valve Status 0 Closed 1 Open 399 1 Bit O C T R DPT_Open...

Страница 31: ..._SceneControl 0 63 128 191 ML General Switch Off Scene Scene Sending 425 1 Byte C T DPT_HVACMode 1 Comfort 2 Standby 3 Economy 4 Building Protection ML General Switch Off HVAC mode Auto Comfort Standb...

Страница 32: ...n and send us your inquiries about Zennio devices http support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio c...

Отзывы: