MAXinBOX Hospitality
Technical Support:
21
Individual outputs
:
short or long pressing the button will commute the on-off
state of the relay.
Shutter channel
: pressing the button will make the shutter drive move
upward or downward (depending on the button) until the button is released
again, thus ignoring the position of the shutter and the parameterised times.
Note
:
after leaving the Test On mode, the status objects will recover the
values they had prior to entering Test On. As the device is never aware of the
actual position of the shutter (as the shutter drive does not provide any
feedback), these values may not show the real position. This can be solved
by performing a complete move-up or move-down order, or by calibrating the
shutter position in the Test On mode until it matches the status objects
.
Fan
: a simple press (short or long) implies an increase or decrease of the fan
speed, depending on the button pressed.
In case the fan coil module is
disabled in parameters
, it will work as non-
cyclical and through relay switching (with a 0.3 s delay).
In
any other case
, the Test On mode will still respect the cyclical / non-
cyclical configuration, and the relay management type parameterised.
Valves
: a simple press (short or long) will make the valve switch its
open/closed state. The behaviour is analogous as for the Test Off mode,
although both valves will be controllable in Test On even if not enabled in
parameters.
Disabled outputs
:
under the Test On mode, short and long presses will
cause the same effect for disabled outputs as for shutter channel outputs
(i.e., the relay will switch its state until the button is released and only one
relay per group is allowed to be closed).
The lock, timer, alarm and scene functions will not work while the device is under the
Test On mode. Status objects will not be sent to the bus, either. However, alarms and
lock orders received during the Test On mode will be taken into account once the
device leaves this mode.