MAXinBOX Hospitality
Technical Support:
22
ETS PARAMETERISATION
The
Manual Control
is configured from a specific tab which can be enabled from the
“General” screen (see section 2.1)
.
Figure 6
Manual Control
The parameters available in this screen are grouped into two sections, as it is possible
to
configure independently the behaviour of the Manual Control for both
, the
fan
coil
and the individual binary outputs:
Mode
: options are “Disabled”, “Only Test Mode Off”, “Only Test Mode On”
and “Test Mode Off + Test Mode On” (default).
Depending on the selection, the device will permit using the manual control
under the Test Off, the Test On, or both modes. Note that, as stated before,
using the Test Off mode does not require any special action, while switching
to the Test On mode does require long-pressing the Prog./Test button.
Lock Manual Control
: unless the above parameter has been set to
“Disabled”, enabling the Lock Manual Control parameter will provide a
runtime procedure for locking the manual control. When this checkbox is
enabled, object “
Manual Control Lock
” turns visible, as well as two more
parameters:
Value
: defines whether the lock/unlock of the manual control should take
place respectively upon the reception (through the aforementioned object)
of values “0” and “1”, or the opposite.
Initialisation
: sets how the manual control should remain after the device
start-up
(after an ETS download or a bus power failure): “Unlocked”,
“Locked” or by default, “Last Value” (unlocked after the first start-up).