![Zennio MAXinBOX Hospitality ZCL-HP126 Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/zennio/maxinbox-hospitality-zcl-hp126/maxinbox-hospitality-zcl-hp126_user-manual_3444038020.webp)
MAXinBOX Hospitality
Technical Support:
20
If the fan is already at the maximum speed level, a further increase will
have no effect (in case of a non-cyclical control) or will switch back to the
minimum level (in case of a cyclical control).
If the fan is already at the minimum speed level, a further decrease will
have no effect (in case of a non-cyclical control) or will switch back to the
maximum level (in case of a cyclical control).
Valve
: a simple press (short or long) will make the valve switch its
open/closed state, provided that the fan coil has been enabled in parameters.
In case the fan coil control type has been configured in parameters as
“applied to the fan” (instead of “applied to the valve”), this may also imply:
A switch-on of the fan
, if it is found to be stopped and the valve opens,
provided that the desired fan speed is other than zero.
A switch-off of the fan
, it is found to be in motion and the valve closes,
provided that the current mode is Heating (under Cooling, the fan will
remain as is).
Disabled output
: outputs disabled in parameters will not react to button
presses under the Test Off mode.
Regarding the lock, timer, alarm and scene functions, the device will behave as usual
under the Test Off mode. Button presses during this mode are entirely analogous to the
reception of the corresponding orders from the KNX bus.
Test On Mode
After entering the Test On mode, it will only be possible to control the outputs through
the on-board pushbuttons. Orders received through communication objects will be
ignored, with independence of the output they are addressed to.
On the other hand, to prevent interference with the normal operation and since the Test
On mode is intended for testing, once the device leaves the Test On mode it will
switch back to its previous state
.
Depending on the parameterisation of the output, the reactions to the button presses
will differ.