Aeon Battery Installation Manual V1.2 JAN 2020 | pg. 21
4
INSTALL
4.4
Connecting and commissioning the battery
Connect the battery according to your specific power equipment requirements and local
standards.
4.4.1
Inverter Settings
Configure standard two or three stage battery chargers/inverters with the settings below to
work with the Aeon Battery. For information on charge and discharge settings for specific
inverters, please contact Zenaji.
High Cut-off Voltage (Bulk/Absorption voltage) ≤ 55.5V
Float Voltage
≤ 54.5V
Low Cut-off Voltage
≥ 42V
Low Restart (Reconnect) Voltage
≥ 45V
4.4.2
Connecting a single battery
When connecting a single battery to power equipment no distribution block is required,
though extra isolation may be required depending on your local regulations. Follow the
instructions in your power equipment installation manual and any local regulations.
4.4.3
Multiple Batteries
When connecting multiple batteries the following must be adhered to
•
Only connect multiple batteries in parallel, Zenaji, connecting batteries in series will
invalidate any warranty claims.
•
When connecting ensure batteries are within ±0.5V of each other. Batteries are
supplied from factory at 46.6V ±0.25V.
•
To connect the battery, connect the positive wire to the positive connection on your
power equipment
4.4.4
Adding a battery to an existing Zenaji battery system
Additional batteries must be within ±0.5V of the installed batteries before connecting to
the battery system. Multiple additional batteries can be connected at once, so long as their
voltages are with ±0.5V of each other.
If the voltage difference between the installed battery and additional battery is greater than
±0.5V they must be balanced. Balancing and connection can be achieved by one of two
methods. In both methods the option to charge or discharge the battery is given, though in
most cases (especially if connected to a grid or a generator) it is easier to charge either the
installed battery or additional battery.
Suggested method choice is shown below.
Installed Battery voltage < Additional battery – use Method 1
Additional Battery voltage < Installed Battery voltage – use Method 2