44 - EN
4. Specifications
4.1 Technical specifications
ComfoVar Aero
Supply Zone 125
Supply Zone 160
performance
Flow rate
30 . . . 220 m³/h
30 . . . 360 m³/h
dimensions
VM width
240 mm
240 mm
number of VMs
2
2
VMs width
480 mm
480 mm
CM width
56 mm
56 mm
CM+VMs width
536 mm
536 mm
VM length
653 mm [excl. adapter]
653 mm
VM depth
199 mm
199 mm
Length of air duct connection
40 mm
40 mm
air ducts
air duct connections
round
round
adapter 125 / 160 mm
yes
no
air duct ø house side
125 mm
160 mm
air duct ø AHU side
125 mm
160 mm
electric
connection voltage AC
230 V AC ± 10%,
(single phase, 50 Hz)
230 V AC ± 10%,
(single phase, 50 Hz)
connection voltage DC
24 V DC SELV
24 V DC SELV
power consumption
5.5 W
5.5 W
material
inside
EPP, ABS, POM, PA 66 EPP, ABS, POM, PA 66
outside
galvanised sheet steel,
EPP, ABS
galvanised sheet steel,
EPP, ABS
various
internal sensor
pressure sensor
pressure sensor
external sensor (optional)
5x 0...10 V DC
(12 V DC) input
5x 0...10 V DC
(12 V DC) input
IP classification (only for CM)
IP32
IP32
Air Leakage-classification
(NEN-EN 1751:2014)
C
C
ISO-classification
B
B
weight of one VM
~ 4 kg
~ 4 kg
total weight (CM+VMs)
~ 8 kg
~ 8 kg
10001124369-0123-zw-zw-A4 ComfoVar Aero Installer_Service Zehnder-General_BOOK_2.indb 44
10001124369-0123-zw-zw-A4 ComfoVar Aero Installer_Service Zehnder-General_BOOK_2.indb 44
24-01-2023 11:11
24-01-2023 11:11