6.3 Configuring the web server
The web server on the CM is only accessible as long as the Wi-Fi is turned on, see paragraph 6.2.
The fresh air values (ventilation values) for the system concerned must be known before configuration. These
differ for each construction project. They are:
■
minimum volume;
■
nominal volume;
■
maximum volume;
■
total volume.
Carry out the configuration only in the vicinity of the air volume controller.
The URL of the embedded web server is: http://172.30.135.1/
Step.
Action
1
Enter the username: admin
2
Enter the password: 4210
3
Select the WIZARD tab
4
Three wizards can be selected:
•
Commissioning;
•
Modbus Internal;
•
Modbus External.
The steps below show the commissioning wizard.