18 - EN
P menus for installer.
Menus without minimum and maximum values are read-only menus.
Menu P3
Setting ventilation programmes
Ventilation programme values
Sub-menu Description
Minimum Maximum
Factory reset
P30
Setting the capacity (in %) of the exhaust fan in
absent setting.
0% or
15%
97%
nL / HL
15% / 15%
P31
Setting the capacity (in %) of the exhaust fan in low
setting.
16%
98%
nL / HL
35% / 40%
P32
Setting the capacity (in %) of the exhaust fan in
normal setting.
17%
99%
nL / HL
50% / 70%
P33
Setting the capacity (in %) of the exhaust fan in high
setting.
18%
100%
nL / HL
70% / 90%
P34
Setting the capacity (in %) of the supply fan in absent
setting.
0% or
15%
97%
nL / HL
15% / 15%
P35
Setting the capacity (in %) of the supply fan in low
setting.
16%
98%
nL / HL
35% / 40%
P36
Setting the capacity (in %) of the supply fan in normal
setting.
17%
99%
nL / HL
50% / 70%
P37
Setting the capacity (in %) of the supply fan in high
setting.
18%
100%
nL / HL
70% / 90%
P38
Current capacity (in %) of the exhaust fan.
Current %
P39
Current capacity (in %) of the supply fan.
Current %
Menu P4
Reading temperatures
Temperature values
Sub-menu
Description
Minimum
Maximum
Factory reset
P40
(Optional)
Current value of TAH
(= Temperature of the Postheater)
Current ˚ C
P41
Comfort temperature
12 ˚C
28 ˚C
20 ˚C
P44
n/a
Current ˚C
P45
Current value of T1
(= Outside air temperature)
Current ˚C
P46
Current value of T2
(= Supply air temperature)
Current ˚C
P47
Current value of T3
(= Stale air temperature)
Current ˚C
P48
Current value of T4
(= Exhaust air temperature)
Current ˚C
P49
n/a
Current ˚C
All temperatures are in degrees Celsius (°C). In the back of this document you
can find an conversion table. (°F = °C × 1.8 + 32)