18 - EN
EN - 19
Menu P5
Setting additional programmes
Additional programme values
Sub-menu
Description
Minimum
Maximum Factory reset
P50
Activation of the
open fire programme.
0 (= No)
1 (= Yes)
0
P51
n/a
0 (= No)
1 (= Yes)
0
P52
n/a
0
3
2
P53
n/a
0 (= No)
1 (= Yes)
0
P54
Confirming the presence of a bypass.
0 (= No)
1 (= Yes)
1
The standard ComfoAir configuration includes a bypass.
Leave the value at “1”.
P55
(Optional)
Confirming the presence of a Postheater.
■
0; Postheater not fitted.
■
1; Postheater fitted.
■
2; Postheater is fitted and is regulated by a Pulse.
Width Modulation (PWM) signal.
0 (= No)
1 (= Yes)
0
P56
Setting the required
air volume in the house.
■
nL: “normal air volume”.
■
HL: “high air volume”.
nL
HL
HL
Note:
Setting the air volume is the starting point for programming the air specifications and setting the
fans.
P57
Setting the ComfoAir type.
■
Li = “Lefthand version”.
■
Re = “Righthand version”.
Li
Re
Li
Note:
The ComfoAir is correctly preprogrammed at the factory.
This setting is lost during a factory reset and will then have to be reprogrammed.
The correct setting can be found on the ComfoAir's identification plate.
P58
Enter controller priorities.
■
0; In the AUTO mode the signals of the analogue
(010V) ports are included when defining the high
setting.
■
1; In the AUTO mode the signals of the analogue
(010V) ports are ignored when defining the high
setting.
0
1
0
Note:
In the MANUAL mode all signals are always included when defining the high setting.
P59
(Optional)
Confirming the presence of an enthalpy exchanger.
■
0; Enthalpy exchanger fitted
■
1; Enthalpy exchanger with RH sensor.
■
2; Enthalpy exchanger without RH sensor.
0 (= No)
2 (= Yes)
0
If an enthalpy exchanger without a sensor is selected, then the protection programme will
not be activated and malfunction alerts EA1 & EA2 will never occur.