20 - EN
P6
Setting additional programmes (Optional)
Additional programme values
Sub-menu Description
Minimum
Maximum
Factory reset
P60
n/a
0 (= No)
3 (= Yes)
0
P61
n/a
0%
99%
0%
P62
n/a
0ºC
15ºC
7ºC
P63
n/a
10ºC
25ºC
23ºC
P64
(Optional)
Tah (= temperature of the Postheater), required
5ºC
40ºC
18ºC
Note:
The Postheater will be deactivated once the set temperature has been reached.
All temperatures are in degrees Celsius (°C). In the back of this document
you can find an conversion table. (°F = °C × 1.8 + 32)
Menu P7
Reading malfunctions (and system information)
(Malfunction) information values
Sub-menu
Description
Minimum
Maximum
Factory
reset
P70
Current software version.
Version number of the software
(without “v”)
P71
Most recent malfunction.
Code in accordance with alarm
and malfunction alert
P72
Second most recent malfunction
Code in accordance with alarm
and malfunction alert
P73
Third most recent malfunction
Code in accordance with alarm
and malfunction alert
P74
Resetting a malfunction
■
Set the value to “1” and press
0
1(= activate)
0
P75
Factory reset
■
Set the value to “1” and press
for at least 5
seconds.
All original software settings are restored following a
factory reset.
0
1(= activate)
0
Note:
After a general reset, the ComfoAir will ask you to reset the “nL / HL” (see P56) and “Li / Re”
(see P57) settings.
After a general reset, all settings and programmes must be checked and set to the correct
values where necessary.