EN - 12
2.5 Configuration of the unit
Legend
ACRONYM
MEANING
R
Right layout
L
Left layout
ODA
Outdoor air intake
SUP
Indoor supply air
ETA
Indoor air extraction
EHA
Outdoor air exhaust
Consider the following schemes to connect the ducts:
R
ODA
SUP
EHA
ETA
ETA
EHA
SUP
ODA
L
2.6 Installation procedure
During the installation, please take into consideration electromagnetic interferences.
■
Ensure that there is a barrier (e.g. separate duct or compartment) or minimum distance
of 150 mm between the interfering power cables (e.g. 230 V) and cables sensitive to
interference (e.g. testing, low voltage, interface, LAN, digital or analogue signal).
■
Make sure interfering and sensitive cables cross each others perpendicularly.
■
Ensure that the cables used for the controls meet the requirements specified in the
section “Technical specifications”.
These measures will limit the EMC disruptions as much as possible and ensure the best communication.
2.6.1 Floor mounting
CAUTION!
Do not connect the ComfoAir Q nor the ComfoClime to the power supply until the
end of the complete installation and the mutual connection of the units is done.
The unit must not be mounted/hung onto the wall.
For the anti-tilt plaque please use proper fastening screws accordingly to the type
of wall.
The installation position must be horizontal.