14
4
Chapter for qualified personnel
Installation
requirements
The following requirements must be assured for the correct installation:
Installation in accordance with the general and locally applicable safety and installation regulations from, among others,
the electric utility, and in accordance with the regulations stipulated in this manual.
Outside wall with final construction thickness of minimum 275 mm.
Sufficient space from objects and for maintenance work (at least 10 cm on extract air side, 20 cm on the supply air
side, 80 cm at the front, and 20 cm above the unit), with regard to the housing surfaces when installed.
Minimum distances on the facade side for outdoor air 10 cm, for exhaust air 20 cm; recommended suction opening for
the outdoor air with respect to the ground >1 m, however, at least unpolluted air in the suction area.
Electrical connection for stationary units for a working voltage range between 100–240 VAC / 50–60 Hz.
Packaging and handling
The ventilation unit and the facade finish are packed in a transport-safe box. Proceed with care when unpacking and
handling the ComfoAir 70.
NOTE
Do not damage or dispose of the packaging before final installation of the ventilation unit.
Checking the scope of delivery
If damages or incompleteness should be determined at the delivered product, please contact the supplier immediately.
Included in the scope of delivery are:
ComfoAir 70, including installation kit
Facade finish including installation set
Mounting template as imprint on the inside of the lid of the box
User
manual
Product labels for energy-efficiency label
Installation
General installation requirements
The following requirements and precautions at the installation site must be taken into account:
WARNING
Observe accident prevention regulations
Observe the accident prevention regulations when setting up the installation site.
Secure the outside area against falling parts.
WARNING
Danger due to escaping gas or electric shock
Make sure that there are no supply lines (e.g. electricity, gas, water) in the area of the external wall opening.
Ensure that the external wall opening meets the static requirements on site.
WARNING
Risk due to electric shock
Observe the country-specific standards/regulations for compliance with the protection areas for installation in rooms
with a bathtub or shower with regard to the IP20 degree of protection applicable to the ventilation unit.
CAUTION
Risk of injury due to falling design cover
The ComfoAir 70 is intended exclusively for installation in an external wall, whereby the housing must be positioned
vertically on the inside of the wall with the exhaust and supply air grilles at the top.
NOTE
The electronics/control unit can be damaged by static charge; which is why you must always take measures to prevent
electrostatic discharge when handling the control unit (e.g. by wearing an anti-static armband).