Refrigeration unit
Series Zero Direct-Drive
Z200 | Z250 | Z350 | Z380
Z380 Multi
INSTALLATION MANUAL
rev.01
47
•
Pass the pipes and the electrical connection cables to the evaporator through the hole on the
roof.
•
Fix the unit with the screws provided.
3.7 Evaporator installation
DANGER
The evaporator contains nitrogen under pressure. Before installation, release the
nitrogen as described in this paragraph.
To install the evaporator proceed as follows:
•
Allow the nitrogen to slowly escape from the suction, liquid, and defrosting lines by loosening the
caps.
•
Remove the evaporator panel to access the fastening holes.
•
Prepare the fastening holes according to the refrigeration unit model and the installation mode
(see. 2.1).
CAUTION
Position the evaporator respecting the distances indicated in the drawings in the chapter
NOTE
Depending on the model and type of installation, the pipes and the electrical connection
cables can be routed alongside the evaporator or through the removable doors.
•
Fix the evaporator with the screws provided.