74
Cooling Circuit
3.9 Scroll Stand-by
Compressor
Stand-by Compressor Replacement
(a)
Open unit top cover (Nose Mount) or open unit
front door (Under Mount).
(b)
Open unit bottom cover.
(c)
Recover refrigerant
3.2.2
Section.
(d)
Close all of compressors Valves.
(e)
Disconnect Unit from Electrical
Supplies (Battery and Electrical
Main).
(f)
Unscrew compressor base from
unit frame.
(g)
Extract/Pull out liquid injection
valve sensing bulb from
compressor head.
(h)
Unscrew, holding valve body, all of
scroll compressor Valves.
CAUTION
!
Do not disconnect
valves from flexible hoses.
Содержание un0 060
Страница 1: ...0MAN295 USA WORKSHOPMANUAL un0...
Страница 4: ......
Страница 15: ......
Страница 16: ......
Страница 17: ...Section1 Generalinformation...
Страница 19: ......
Страница 30: ......
Страница 31: ...Section2 Descriptionoftheunit...
Страница 33: ......
Страница 37: ...26 Description of the unit 2 1 Condensing unit Under Mount Discharge line Suction line Heat defrost line...
Страница 45: ...34 Description of the unit 2 2 Evaporating section...
Страница 46: ......
Страница 47: ...Section3 CoolingCircuit...
Страница 94: ......
Страница 95: ...Section4 DieselEngine...
Страница 97: ......
Страница 98: ...87 4 1 Belts Diesel Engine 4 Diesel Engine 4 1 Belts Individual Protection Devices Googles Gloves Proper tools...
Страница 130: ......
Страница 131: ...Section5 ElectronicsandWirings...
Страница 135: ......
Страница 146: ...135 5 2 Electronic Boards Electronics and wiring 5 2 Electronic Boards CPU board...
Страница 150: ...139 5 2 Electronic Boards Electronics and wiring Relay Board...
Страница 155: ...144 Electronics and wiring 5 2 Electronic Boards Low Voltage Wirings...
Страница 156: ...145 5 2 Electronic Boards Electronics and wiring High Voltage Wirings...
Страница 178: ......
Страница 179: ...Section6 Alarms Troubleshooting...
Страница 181: ......
Страница 183: ...172 Alarms Troubleshooting 6 1 StandardAlarms A04 Low Pressure Switch...
Страница 184: ...173 6 1 StandardAlarms Alarms Troubleshooting A07 Water Temperature A08 Door Microswitch...
Страница 185: ...174 Alarms Troubleshooting 6 1 StandardAlarms A10 Oil Pressure...
Страница 186: ...175 6 1 StandardAlarms Alarms Troubleshooting A11 High Pressure...
Страница 187: ...176 Alarms Troubleshooting 6 1 StandardAlarms A14 Net compressor high temperature A15 Low Battery...
Страница 188: ...177 6 1 StandardAlarms Alarms Troubleshooting A16 Engine Failure...
Страница 189: ...178 Alarms Troubleshooting 6 1 StandardAlarms A17 Alternator Failure...
Страница 190: ...179 6 1 StandardAlarms Alarms Troubleshooting A18 Water sensor error...
Страница 193: ...182 Alarms Troubleshooting 6 3 Troubleshooting 6 3 Troubleshooting Condenser fan is not running...
Страница 194: ...183 6 3 Troubleshooting Alarms Troubleshooting Evaporator fan is not running F20 Fuse blows often...
Страница 195: ...184 Alarms Troubleshooting 6 3 Troubleshooting Unit does not start after blackout...
Страница 196: ...185 6 3 Troubleshooting Alarms Troubleshooting Unit not performing...
Страница 197: ......
Страница 198: ......
Страница 199: ...Annex1 Parameters...
Страница 201: ......
Страница 208: ......
Страница 209: ......