166
Electronics and wiring
5.8 Running logic
Automatic Cooling Mode Operation Sequence
When running in Automatic Mode, unit stops operations every time cold-room reaches SP set-point temperature, waiting that
difference between TA actual and SP set-point temperatures exceeds dF differential to restart with required operations.
1
ON Signal.
1(’)-2 Starting Procedure.
2-3
Cooling Operations.
3
TA Cold-room temperature has
reached SP set-point value.
3-1’ Unit Stand-by, waiting for
cooling/heating request.
1’ TA Cold-room temperature is out
from admitted range (SP±dF).
4 OFF Signal.
Continuous Cooling Mode Operation Sequence
1 ON Signal.
1-2 Starting Procedure.
2-3 High Speed Pull Down.
3 TA-SP<ddF Engine decreases speed.
3-4 Unit Cools cold-room at Slow speed.
4 Unit starts to heat.
4-5 Unit Heats at Slow speed.
5 Unit starts to Cool.
5-4
Unit Cools at Slow speed.
2’
TA-SP>ddF Engine increases speed.
2’-3 High Speed Cooling.
6 Heating unit increases speed.
6-7
High Speed Heating.
7
Unit decreases speed.
7-5
Unit Heats at Slow speed.
8
OFF Signal.
Содержание un0 060
Страница 1: ...0MAN295 USA WORKSHOPMANUAL un0...
Страница 4: ......
Страница 15: ......
Страница 16: ......
Страница 17: ...Section1 Generalinformation...
Страница 19: ......
Страница 30: ......
Страница 31: ...Section2 Descriptionoftheunit...
Страница 33: ......
Страница 37: ...26 Description of the unit 2 1 Condensing unit Under Mount Discharge line Suction line Heat defrost line...
Страница 45: ...34 Description of the unit 2 2 Evaporating section...
Страница 46: ......
Страница 47: ...Section3 CoolingCircuit...
Страница 94: ......
Страница 95: ...Section4 DieselEngine...
Страница 97: ......
Страница 98: ...87 4 1 Belts Diesel Engine 4 Diesel Engine 4 1 Belts Individual Protection Devices Googles Gloves Proper tools...
Страница 130: ......
Страница 131: ...Section5 ElectronicsandWirings...
Страница 135: ......
Страница 146: ...135 5 2 Electronic Boards Electronics and wiring 5 2 Electronic Boards CPU board...
Страница 150: ...139 5 2 Electronic Boards Electronics and wiring Relay Board...
Страница 155: ...144 Electronics and wiring 5 2 Electronic Boards Low Voltage Wirings...
Страница 156: ...145 5 2 Electronic Boards Electronics and wiring High Voltage Wirings...
Страница 178: ......
Страница 179: ...Section6 Alarms Troubleshooting...
Страница 181: ......
Страница 183: ...172 Alarms Troubleshooting 6 1 StandardAlarms A04 Low Pressure Switch...
Страница 184: ...173 6 1 StandardAlarms Alarms Troubleshooting A07 Water Temperature A08 Door Microswitch...
Страница 185: ...174 Alarms Troubleshooting 6 1 StandardAlarms A10 Oil Pressure...
Страница 186: ...175 6 1 StandardAlarms Alarms Troubleshooting A11 High Pressure...
Страница 187: ...176 Alarms Troubleshooting 6 1 StandardAlarms A14 Net compressor high temperature A15 Low Battery...
Страница 188: ...177 6 1 StandardAlarms Alarms Troubleshooting A16 Engine Failure...
Страница 189: ...178 Alarms Troubleshooting 6 1 StandardAlarms A17 Alternator Failure...
Страница 190: ...179 6 1 StandardAlarms Alarms Troubleshooting A18 Water sensor error...
Страница 193: ...182 Alarms Troubleshooting 6 3 Troubleshooting 6 3 Troubleshooting Condenser fan is not running...
Страница 194: ...183 6 3 Troubleshooting Alarms Troubleshooting Evaporator fan is not running F20 Fuse blows often...
Страница 195: ...184 Alarms Troubleshooting 6 3 Troubleshooting Unit does not start after blackout...
Страница 196: ...185 6 3 Troubleshooting Alarms Troubleshooting Unit not performing...
Страница 197: ......
Страница 198: ......
Страница 199: ...Annex1 Parameters...
Страница 201: ......
Страница 208: ......
Страница 209: ......