2-1 Auto Report
2-1-1 Time Interval
The Temp./Humid. Detector can be set to emit report of current status to
the nodes of Grouping 1 automatically at a set time. The time interval
can be set from 1 minute to 24 hours. For instance, if time interval is
set in 1 minute, the detector will report its status once per minute.
Please refer to the parameter 6 of configuration table on page 6.
2-1-2 Temperature Change
The Temp./Humid. Detector can be set to emit report of temperature
status to the nodes of Grouping 1 automatically once the temperature
changing exceeds set degree. The temperature difference range can
be set from 1
。
C to 70
。
C . For instance, if temperature difference is set in
1
。
C , the detector will report its current temperature status once the
temperature difference exceeds 1
。
C . Please refer to the parameter 7 of
configuration table on page 6.
2-1-3 Change of Humidity
The Temp./Humid. detector can be set to emit report of humidity status
to the nodes of Grouping 1 automatically once the humidity change
exceeds set %RH. The humidity difference range can be set from
5%RH to 70%RH. For instance, if humidity difference is set in 5%RH,
the detector will report its current humidity status once the humidity
difference exceeds 5%RH. Please refer to the parameter 8 of
configuration table on page 6.
Note:
Auto report mechanism may cause a lot of power consumption if it
operates regularly. Please base on actual requirements for determining whether
to enable the function of auto report.
2-2 Wakeup Configuration
The Temp./Humid. Detector stays in sleep status for the majority of time in
order to conserve battery power. However, it can be woken up by either
triggers of temp./humid. or set time for the controller to do further setting.
2-2-1 Wakeup Time Interval
The detector stays in wakeup status for 10 seconds. If the detector
receives RF command from the controller during these 10 seconds, it will
extend waking time for another 10 seconds until no more RF command is
received. Once the wakeup time is up, the detector goes back to sleep
status.
2-2-2 Sleep Time Interval
The sleep interval can be set from 1 minute to 4660 hours (about 194
days). The unit of time is in seconds. The preset sleep time interval is 1
hour.
3. Command Classes
The Temp./Humid. Detector supports Command Classes including…
*
COMMAND_CLASS_BASIC
* COMMAND_CLASS_VERISON
* COMMAND_CLASS_BATTERY
* COMMAND_CLASS_WAKE_UP_V2
* COMMAND_CLASS_CONFIGURATION
* COMMAND_CLASS_ASSOCIATION_V2
* COMMAND_CLASS_MANUFACTURER_SPECIFIC
* COMMAND_CLASS_SENSOR_MULTILEVEL_V2
* COMMAND_CLASS_MULTI_INSTANCE_V2
Troubleshooting
Symptom Possible
Cause
Recommendation
LED cannot be displayed
1. Run out of battery
power.
2. Check if reverse
battery polarity
1. Replace a new battery
2. Refit the battery with
correct polarity
Temperature/humidity
reading is incorrect
The Detector is out of
order
1. Please leave the detector
without operating or do any
setting for a period
2. Do not open the detector;
send it to the local retailer.