5

Note:

 

 

The humidity of trigger-ON and trigger-OFF cannot be set equal; there MUST 
be at least

 5% 

difference in between. For example, if now the trigger-ON 

humidity is already set to be 50%, so trigger-OFF humidity can only be 

45% 

or 

55%. (Values between 45% and 55% cannot be set.) 

 

 

Once the detector has been triggered, the humidity must raise up or drop down 
at least

 5% 

from the preset value before it can be triggered again. For example, 

if the detector has been triggered on at 50%, then the temperature must be 

55% or 

45% before it can be re-triggered. 

 

3. Radio Frequency 

 
This function is designed to enable or disable the sending of RF command which 
comprised of Z-wave protocol to the associated nodes, as Temp./Humid. 
Detector has been triggered on/off. 
 
Press 

 and select MODE 7, the icon 

 should flash. Press 

 to 

turn On (enable) the function or 

  to turn OFF (disable) the function. 

 

Note: 

 

If the RF mode is OFF, no command will be sent even the Temp./Humid. 

Detector has been triggered.  If RF is ON and the detector has been 
triggered, the RF command will be sent to nodes of Grouping 2. 

 

 

If the RF reading is 00, it implies no node ID has been allocated by Z-Wave 

Controller.    Please execute inclusion mode as described on page 1. 

 
4. Beep Tone 
 

To set the beep tone, press 

 and select MODE 8. The icon 

 flashes. 

Press 

  for ON and 

  for OFF. If it is ON, a beep tone will be sounded 

whenever a button is pressed; 4 continuous beep tones will be sounded for 1 
second if the detector has been triggered. 
 

Programming

 

 

1. Z-Wave’s Groups (Association Command Class Version 2) 

 
The Temp./Humid. Detector can be set to send reports to or control associated 
Z-Wave devices.    It supports two association groups with one node support for 
Grouping 1 and three nodes support for Grouping 2. 
 
Grouping 1 includes POWER_APPLIED, SENSOR_MULTILEVEL _REPORT, 
ALARM_REPORT an d BATTERY_REPORT_COMMAND 
 
Grouping 2 includes BASIC_SET 

1-1 Grouping 1 (Max. Node = 1) 
 

1-1-1 POWER_APPLIED command 

 
Whenever power is applied, it will send ALARM_REPORT command to 
the nodes of Grouping 1 to inform the devices that the detector is 
powered up. 

 

ALARM_REPORT Command 

[Command Class Alarm, Alarm Type = 0x02, Alarm Level = 
0x01] 

 

1-1-2 MULTILEVEL_SENSOR_REPORT 

 

The detector will emit SENSOR_MULTILEVEL_REPORT to inform the 
nodes of Grouping 1 automatically its current temperature and humidity.   
Refer to the section of Z-Wave’s Configuration as described on page 6 
for settings of auto report configuration. 
 

 1-1-2-1 

Humidity 

 

SENSOR_MULTILEVEL_REPORT 

[Command Class Sensor Multilevel, Sensor Multilevel 
Report, Sensor Type = 0 x 05 (Relative Humidity), 
PrScale+Size = 0 x 01, Sensor Value 1 = 20-90%] 

 

 

 

 

  

 

Example: 

 

 

 

Sensor Value 1 = 0x23 

 

 

 

Humidity Value = Sensor Value = 35 (%) 

 
 1-1-2-2 

Temperature 

(Celsius) 

 

SENSOR_MULTILEVEL_REPORT 

[Command Class Sensor Multilevel, Sensor Multilevel 
Report, Sensor Type = 0 x 01 (Air Temperature), 
PrScale+Size = 0 x 22, Sensor Value 1 = (High 
Byte of Temperature Value), Sensor Value 2 = (Low Byte 
of Temperature Value)] 

 
  

 

Example: 

 

 

 

Sensor Value 1 = 0x01 

 

 

 

Sensor Value 2 = 0x31 

 

Temperature (C)  = (Sensor Value 1*256 + Sensor Value 2)/10 

 

 

     

(1*256+49)/10 

30.5 

(C) 

   

 1-1-2-3 

Temperature 

(Fahrenheit) 

Содержание ST814

Страница 1: ...Exclude from a Z WaveTM Network One of function key is used to carry out inclusion exclusion association and reset When the detector is first powered up the reading in RF mode is 00 which implies that...

Страница 2: ...cation on the wall Through the 2 screw holes of the bracket mark the mounting surface with a pencil 2 Where marked drill holes into mounting surface using an appropriate size drill bit and insert the...

Страница 3: ...imit Warning If the temperature is reaching the limit the icon of MAX or MIN will be displayed on the screen Ice Warning If the temperature falls to 0 C temperature display will illuminate with LCD ba...

Страница 4: ...record press both or at the same time Threshold Limit Warning If the humidity is reaching the limit the icon of MAX or MIN will be displayed on the screen Humidity Trigger ON Press and select MODE 5...

Страница 5: ...tor has been triggered Programming 1 Z Wave s Groups Association Command Class Version 2 The Temp Humid Detector can be set to send reports to or control associated Z Wave devices It supports two asso...

Страница 6: ...n parameter 1 for the setting of basic set command 2 Z Wave s Configuration The table below lists the configuration parameters and the value range for users to set up the detector Parameter Function S...

Страница 7: ...regularly Please base on actual requirements for determining whether to enable the function of auto report 2 2 Wakeup Configuration The Temp Humid Detector stays in sleep status for the majority of t...

Страница 8: ...ng measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the rec...

Отзывы: