Integer Registers
The integer data type could be used for the Results data and configuration/control parameters.
The “holding registers” as referred to by the Modbus specification, are read/write registers. This
16-bit integer data type can be manipulated using functions 3, 6, and 16.
Function 3
allows the host to read one or more holding registers per query.
Function 6
allows the host to write a single holding register per query.
Function 16
allows the host to write multiple holding registers per query.
Result Data Functions
The result data functions available via Modbus are listed below. The registers are accessed using
Modbus function 3. If variable type is not specified, the default variable type is a 16 bit unsigned
integer.
Address
Access
Descriptions
40001-40002
Read Only
Most-recent HOU/LOU accumulated odorant injected (IEEE 754
floating-point format, most-significant word first)
40003-40004
Read Only
Most-recent HOU/LOU accumulated flow (IEEE 754 floating-point
format, most-significant word first)
40005-40006
Read Only
Most-recent HOU/LOU average injection rate (IEEE 754 floating-point
format, most-significant word first)
40007
Read Only
Most-recent HOU/LOU Start Date - Day of Month
40008
Read Only
Most-recent HOU/LOU Start Date - Month
40009
Read Only
Most-recent HOU/LOU Start Date - Year
40010
Read Only
Most-recent HOU/LOU Start Date - Hours (24 hour format)
40011
Read Only
Most-recent HOU/LOU Start Date - Minutes
40012
Read Only
Most-recent HOU/LOU Start Date - Seconds
40013
Read Only
Most-recent HOU/LOU End Date - Day of Month
40014
Read Only
Most-recent HOU/LOU End Date - Month
40015
Read Only
Most-recent HOU/LOU End Date - Year
40016
Read Only
Most-recent HOU/LOU End Date - Hours (24 hour format)
40017
Read Only
Most-recent HOU/LOU End Date - Minutes
40018
Read Only
Most-recent HOU/LOU End Date - Seconds
40019-40020
Read Only
System odorant injected totalizer (IEEE 754 floating-point format,
most-significant word first)
40021-40022
Read Only
Serial Number (32-bit unsigned integer, most-significant word first)
40023
Read Only
Model Number (6400, 7400, 8400, 9400)
40024
Read Only
Process Type (1 = Gas, 2 = Liquid, 3 = Liquid Continuous)
40025
Read Only
Bulk tank level (0-100 %)
40026
Read Only
Odorant inlet pressure (XXX.X PSI; X.XXX Bar)
40027
Read Only
Verometer level (XXX.X %) (16-bit signed integer)
40028
Read Only
Odorant temperature (XX.X F/C) (16-bit signed integer)
40029
Read Only
Flow signal (XX.X %)
40030
Read Only
ACC output current (X.XX mA)
40031
Read Only
Measured pump capacity (XXX.X %)
40032-40033
Read Only
1 hour time-based injection rate average (IEEE 754 floating-point
format, most-significant word first)