YZ Systems, Inc. • 3101 Pollok Drive • Conroe, Texas • USA • 77303 • P: 936.788.5593 • F: 936.788.5720
Page 92
NJEX 8300 ver .092001 ATEX Rev.
SSSSS
ECTION
ECTION
ECTION
ECTION
ECTION
13:
13:
13:
13:
13: 8300 S
8300 S
8300 S
8300 S
8300 S
Y
YY
Y
YSTEM
STEM
STEM
STEM
STEM
TTTTT
R
RR
R
ROUBLESHOO
OUBLESHOO
OUBLESHOO
OUBLESHOO
OUBLESHOOTING
TING
TING
TING
TING
IMPOR
IMPOR
IMPOR
IMPOR
IMPORTTTTTANT NO
ANT NO
ANT NO
ANT NO
ANT NOTE:
TE:
TE:
TE:
TE:
When a system re-start is requested at completion or during
the the service of an NJEX System, use the N-300 controller
to stop and restart the system from the main menu.
After a restart, the default values will be used for opera-
tion, and alarms will be cleared until actual performance
values can be ascertained by the N-300 controller. In the
case of the pump displacement this may not occur until
the pump has drained the Verometer to approximately
the 90% level. An * will appear by the indicated pump
displacement after a stop and restart. This indicates that
the displayed value is a default parameter value, which
is not a real pump performance indication. As a result,
this defualt pump performance indication should not be
relied upon as the actual pump performance.
Do not prematurely assume the problem has been resolved,
simply due to the disappearance of the indicators and alarms
immediately after a re-start of the NJEX System.
Specific Pump Over Pumping Alarm
Issues Troubleshooting Steps
When an active
Over Pumping
alarm is indicated the
following steps should be taken:
1. This alarm may occur after service or maintenance
has been performed due to variances in the
Verometer level during the conduct of service. If
service has recently been performed, and this alarm
occurs, stop and restart the system to observe if the
alarm re-occurs, thus indicating a real alarm. If the
alarm re-occurs continue to step 2 below.
2. Verify that the operating conditions remain un-
changed and correct as needed. The pipeline
pressure should be at least 250 psi
(17.24 Bar)
.
a. Inspect the installation for the use of a back
pressure regulating device. For pipeline pres-
sures less than 250 psi
(17.24 Bar)
a back
pressure regulating device must be installed
immediately outside the NJEX enclosure on the
odorant line leading to the pipeline injection
point. A back pressure regulating device can
aliviate the over pumping conditions that can
result by the varying pressures and tempera-
tures in the pipeline for pressures less than 250
psi
(17.4 Bar)
. If a back pressure regulating
device is not installed as described above,
install the device before proceeding.
b. If line pressure is less than 250 psi
(17.24 Bar)
and a back pressure regulating device is
installed on the odorant injection line, inspect
the back pressure regulating device for proper
operation, and installation as described above.
3. Verify that the actuation pressure remains un-
changed from previous setting.
4. Verify the pump displacement parameter setting is
the same as the desired pump displacement.
Specific Pump Under Pumping Alarm
Issues Troubleshooting Steps
When an active
Under Pumping
alarm is indicated the
following steps should be taken:
1. If maintenance or repair has just been performed,
stop and restart the system to see if the alarm re-
occurs indicating a real alarm. If the alarm re-occurs
continue to the next step.
2. Verify operating conditions. Correct as needed.
3. Verify that the pump displacement parameter
matches the accurate pump displacement.
Note: When starting a system for the first time the
expected pump displacement should be set in the N300G
controller parameters section. The system should then be
run through at least one complete Verometer cycle to get
an accurate pump displacement reading. Actual installa-
tion conditions may have an effect on the real pump
performance. Use the accurate pump displacement as
calculated by the controller for the final pump displace-
ment parameter to be entered into the controller.
4. Check to see if the pump operation sounds the same as
previously. A distinct bottoming of the plunger piston and