YZ Systems, Inc. • 3101 Pollok Drive • Conroe, Texas • USA • 77303 • P: 936.788.5593 • F: 936.788.5720
Page 39
NJEX 8300 ver.092001 ATEX Rev.
SSSSS
ECTION
ECTION
ECTION
ECTION
ECTION
7:
7:
7:
7:
7: C
C
C
C
C
ALIBRA
ALIBRA
ALIBRA
ALIBRA
ALIBRATING
TING
TING
TING
TING
S
S
S
S
S
IGN
IGN
IGN
IGN
IGNAL
AL
AL
AL
AL
I
I I
I
I
NPUTS
NPUTS
NPUTS
NPUTS
NPUTS
Analog Flow Input Calibration,
1-5 VDC / 4-20 mA
IMPOR
IMPOR
IMPOR
IMPOR
IMPORTTTTTANT
ANT
ANT
ANT
ANT:::::
Many factors effect the signal between the signal source
and the NJEX System. Elements of the signal electrical
system such as the gauge and length of the wire, isolation
barrier, grounding, transient voltages, and the condition of
the signal generated by the flow device can effect the
signal and how that signal is received by the NJEX
System. To truly calibrate the NJEX System to the signal,
use only the flow equipment that will be part of the
odorization system such as; a flow computer, RTU, PLC,
pulse index drive, or differential pressure transducer.
Choose *Set in the main menu,
figure 73.
Choose *Cal in the set selection menu,
figure 74.
Choose *Inputs in the calibration set menu,
figure 75.
Choose *Flow in the calibration selection menu,
figure 76.
Choose *Ang in the flow input type menu, for analog
voltage or current inputs, i.e., 1-5VDC or 4-20mA,
figure 77.
Choose *Lin for input signals that are linear with respect
to flow i.e., flow computers, RTU's, etc,
figure 78.
-OR-
Choose *NonLin for input signals that are non-linear
with respect to flow i.e., differential pressure transmit-
ters, etc.,
figure 78.
Choose *Zero to calibrate the zero set point,
figure 79.
Zero Adjustment,
figure 80, is used to calibrate the N-
300G controller for 0% of the metered flow in the pipeline.
The N-300G is factory calibrated for 0% of flow to directly
correspond to 1.00 VDC
(4.0 mA) at the flow input
terminal board TB1 terminals #2 and #3,
refer to the
Wiring Control Document on page 117 in Appendix D.
Or
Figure 73
pmp bat vmtr sig tnk
PropFlow
Idle
*Strt *Dsp *Set
pmp bat vmtr sig tnk
Set Selection
*Par *Cal *Esc
pmp bat vmtr sig tnk
Calibration Set
*Clk *Inputs *Esc
pmp bat vmtr sig tnk
Calibration
*Flow *Pres *Esc
pmp bat vmtr sig tnk
Flow Input Type
*Ang *Pulse *Esc
pmp bat vmtr sig tnk
Analog Input
*Lin *NLin *Esc
pmp bat vmtr sig tnk
Linear Input
*Zero *Span *Esc
pmp bat vmtr sig tnk
Non Linear Input
*Zero *Span *Esc
Or
pmp bat vmtr sig tnk
Zero Adjustment
*Read 1.0V *Esc
Figure 74
Figure 75
Figure 76
Figure 77
Figure 78
Figure 79
Figure 80