Or
To View Real Time Displays
Choose
*Dsp
in the main menu,
figure 117
.
Strokes signaled
are
the number of pump strokes signaled
by the N-300G controller are shown in this display,
figure 118
.
To reset strokes signaled,
press the
*Rst
key and
follow instructions,
figures 119-119a.
Odorant Injected,
figure 120,
is the cumulative total of
odorant injected in lbs.
(kg)
is shown in this display.
To reset lbs.
(kg) injected,
figures 121,
press the
*Rst
key and follow instructions,
figures 121-121a.
Note: Pounds – lbs. (kg) injected will increment only
when a valid pump displacement has been calculated.
Pounds – lbs. (kg) injected will not increment during fill
valve alarm condition.
Pump Displacement
This display illustrates the last value, in cc / stroke,
calculated by the N-300G with volume data supplied by
the Verometer,
figure 122
.
Note: an asterisk “*” following the value illustrated in the
display designates that a value has not been calculated
at present, and the previously set or programmed pump
displacement will be displayed,
refer to the Program-
ming Sections 5 & 6, beginning on pages 25 & 33.
Pump Alarms
There are three conditions that will result in a pump alarm
indication.
•
Over Pumping,
figure 123,
the calculated pump dis-
placement exceeds the set pump displacement by 30%.
•
Under Pumping,
figure 124,
the calculated pump displace-
ment is less than the set pump displacement by 30%.
•
Pump Failure,
figure 125,
the calculated pump
displacement is less than the set pump displacement
by 75%. For example, low displacement due to an
empty meter, the pump cannot inject odorant when
required if the meter which supplies the odorant to the
pump is empty.
Figure 117
pmp bat vmtr sig tnk
PropFlow
Idle
*Strt *Dsp *Set
Figure 118
Figure 119
Figure 119a
pmp bat vmtr sig tnk
6.000 cc/Stroke *
Pump Displacement
pmp bat vmtr sig tnk
Reset Strokes?
*No *Yes
pmp bat vmtr sig tnk
Strokes Signaled
*Reset 01169284
pmp bat vmtr sig tnk
Strokes Signaled
*Reset 00000000
pmp bat vmtr sig tnk
Odorant Injected
*Reset 0.000lbs
pmp bat vmtr sig tnk
Odorant Injected
*Reset 0.000kg
pmp bat vmtr sig tnk
Reset lbs Injected?
*No *Yes
pmp bat vmtr sig tnk
Reset kg Injected?
*No *Yes
pmp bat vmtr sig tnk
Odorant Injected
*Reset 83.601lbs
pmp bat vmtr sig tnk
Odorant Injected
*Reset 1628.082kg
pmp bat vmtr sig tnk
4.00 cc/Stroke
Pump Displacement
pmp bat vmtr sig tnk
PropFlow
Idle
*Strt *Dsp *Set
Under Pump
Pump Failure
Figure 120
Figure 121
Figure 121a
Figure 122
Figure 123
Figure 124
Figure 125
pmp bat vmtr sig tnk
8.000 cc/Stroke
Pump Displacement
Over Pump